HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
HGM8156 Genset Parallel (With Mains) Controller 2019-09-10 Version 1.1 Page 24 of 44
No.
Items
Range
Defaults
Description
Digital Input Port 2
1
Contents Setting
(0~55)
0
User defined
2
Active Type
(0~1)
0
0: Close
1: Open
3
Active Range
(0-2)
2
0: Active in parallel running
1: Always active
2: Never
4
Active Action
(0-3)
3
0: Warn
1: Trip and Stop
2: Trip
3: Indication
5
Delay
(0-20.0)s
2.0
Time from input port is detected active to
confirm.
6
Description
When input port is active, LCD will display
the content.
Digital Input Port 3
1
Contents Setting
(0~55)
0
High temperature shutdown
2
Active Type
(0~1)
0
0: Close
1: Open
3
Active Range
(0-2)
2
0: Active in parallel running
1: Always active
2: Never
4
Active Action
(0-3)
3
0: Warn
1: Trip and Stop
2: Trip
3: Indication
5
Delay
(0-20.0)s
2.0
Time from input port is detected active to
confirm.
6
Description
When input port is active, LCD will display
the content.
Digital Input Port 4
1
Contents Setting
(0~55)
13
Gen close status
2
Active Type
(0~1)
0
0: Close
1: Open
Digital Input Port 5
1
Contents Setting
(0~55)
0
User defined.
2
Active Type
(0~1)
0
0: Close
1: Open
3
Active Range
(0~2)
2
0: Active in parallel running
1: Always active
2: Never
4
Active Actions
(0~3)
3
0: Warn