HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 63 of 69
Engine type: Common J1939
14.8
DETROIT DIESEL DDEC III / IV
Table 31 - Engine CAN Connector
Terminals of controller
CAN port of engine
Remark
Fuel relay output
Expand 30A relay, battery
voltage of ECU is supplied
by relay.
Start relay output
-
Connect to starter coil directly.
CAN GND
-
CAN communication shielding line
(connect with controller‘s terminal only).
CAN(H)
CAN(H)
Using impedance 120Ω connecting line.
CAN(L)
CAN(L)
Using impedance 120Ω connecting line.
Engine type: Common J1939
14.9
DEUTZ EMR2
Table 32 - F Connector
Terminals of controller
F connector
Remark
Fuel relay output
Expand 30A relay, battery
voltage of 14 is supplied
by relay. Fuse is 16A.
Start relay output
-
Connect to starter coil directly.
-
1
Connect to battery negative pole.
CAN GND
-
CAN communication shielding line
(connect with controller‘s terminal only).
CAN(H)
12
Impedance 120Ω connecting line is
recommended.
CAN(L)
13
Impedanc
e 120Ω connecting line is
recommended.
Engine type: VolvoEDC4
14.10
JOHN DEERE
Table 33
– 21-Pin Connector
Terminals of controller
21 pins connector
Remark
Fuel relay output
G,J
Start relay output
D
CAN GND
-
CAN communication shielding line (connect
w
ith controller‘s terminal only).
CAN(H)
V
Using impedance 120Ω connecting line.
CAN(L)
U
Using impedance 120Ω connecting line.
Engine type: John Deere