HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 31 of 69
No.
Items
Parameters
Defaults
Description
set value.
(0-200)%
105
Set value is DC generator
rated voltage‘s
percentage; when alarm is active, and
voltage is below the return value, alarm
can be cleared automatically.
(0-3600)s
5
Alarm starts when voltage gets up to the
alarm value and this delay is expired.
11
Under Voltage
Warn
0: Disable
1: Enable
0
Alarm is detected after enabled; not
detected if it is disabled.
(0-200)%
90
Set value is DC generator
rated voltage‘s
percentage, alarm starts if it is below the
set value.
(0-200)%
95
Set value is DC generator
rated voltage‘s
percentage; when alarm is active, and
voltage is above the return value, alarm
can be cleared automatically.
(0-3600)s
5
Alarm starts when voltage gets up to the
alarm value and this delay is expired.
12
Over Current
0: Disable
1: Enable
1
Alarm is detected after enabled; not
detected if it is disabled.
(0-200)%
110
Set value is DC generator
rated voltage‘s
percentage, alarm starts if it is above the
set value.
0: Warn
1: Shutdown
2: Trip and Stop
3: Trip
0
Alarm type is optional; if alarm is active,
handle the alarm based on alarm type.
(0-3600)s
5
Alarm starts when current gets up to the
alarm value and this delay is expired.
13
Over Power
0: Disable
1: Enable
1
Alarm is detected after enabled; not
detected if it is disabled.
(0-200)%
110
Set value is DC generator
rated voltage‘s
percentage, alarm starts if it is above the
set value.
(0-200)%
90
Set value is DC generator
rated voltage‘s
percentage; when alarm is active, and
voltage is below the return value, alarm
can be cleared automatically.
0: Warn
1: Shutdown
2: Trip and Stop
3: Trip
0
Alarm type is optional; if alarm is active,
handle the alarm based on alarm type.
(0-3600)s
5
Alarm starts when power gets up to the
alarm value and this delay is expired.