HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 64 of 69
14.11
MTU MDEC
Suitable for MTU engines, 2000 series, 4000series
Table 34 - X1 Pin Connector
Terminals of controller
X1 connector
Remark
Fuel relay output
BE1
Start relay output
BE9
CAN GND
E
CAN communication shielding line (connect
with one terminal only).
CAN(H)
G
Using impedance 120Ω connecting line.
CAN(L)
F
Using impedance 120Ω connecting line.
Engine type: mtu-MDEC-303
14.12
MTU ADEC(SMART MODULE)
It is suitable for MTU engine with ADEC (ECU8) and SMART module.
Table 35 - ADEC(X1 Connector)
Terminals of controller
ADEC (X1port)
Remark
Fuel relay output
X1 10
X1 Terminal 9 connected to negative of
battery
Start relay output
X1 34
X1 Terminal 33 connected to negative of
battery
Table 36 - ADEC(X4 Connector)
Terminals of controller
SMART (X4 port)
Remark
CAN GND
X4 3
CAN communication shielding line (connect
to controller‘s this terminal only).
CAN(H)
X4 1
Using impedance 120Ω connecting line.
CAN(L)
X4 2
Using impedance 120Ω connecting line.
Engine type: mtu-ADEC
14.13
MTU ADEC (SAM MODULE)
It is suitable for MTU engine with ADEC (ECU7) and SAM module.
Table 37 - ADEC (X1 Connector)
Terminals of controller
ADEC (X1port)
Remark
Fuel relay output
X1 43
X1 Terminal 28 connected to negative of
battery.
Start relay output
X1 37
X1 Terminal 22 connected to negative of
battery.
Table 38 - SAM (X23 Connector)
Terminals of controller
SAM (X23 port)
Remark
CAN GND
X23 3
CAN communication shielding line (connect
with controller‘s this terminal only).
CAN(H)
X23 2
Using impedance 120Ω connecting line.
CAN(L)
X23 1
Using impedance 120Ω connecting line.
Engine type: Common J1939