HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 50 of 69
8.3
DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (All Active when connect to
Ground (B-))
Table 15 - Defined Contents of Programmable Inputs
No.
Type
Description
0
Users Configured
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and shutdown after
hi-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run delay.
1
Reserved
2
Alarm Mute
Can prohibit ―Audible Alarm‖ output when input is active.
3
Reset Alarm
Can reset shutdown alarm and trip alarm when input is active.
4
60Hz Active
Use for CANBUS engine and it is 60Hz when input is active.
5
Lamp Test
All LED indicators are illuminated when input is active.
6
Panel Lock
All buttons in panel are inactive except navigation and exit
buttons and there is
on the right of first row in LCD when
input is active.
7
War Mode
All shutdown alarms except alarms of emergency stop and
over speed shutdown cannot stop the engine in the war
mode.
8
Idle Mode
Under voltage/frequency/speed protection is inactive.
9
Auto Stop Inhibit
In
Auto
mode, during generator normal running, when input
is active, inhibit generator shutdown automatically.
10
Auto Start Inhibit
In
Auto
mode, inhibit generator start automatically when input
is active.
11
Scheduled Run Inhibit
In
Auto
mode, inhibit scheduled run genset when input is
active.
12
Reserved
13
Generator Close Status
Connect generator loading switch‘s Aux. Point.
14
Generator Load Inhibit
Prohibit genset switch on when input is active.
15
Reserved
16
Reserved
17
Auto Mode Lock
When input is active, controller enters into auto mode; mode
selection buttons are inactive.
18
Auto Mode Inhibit
When input is active, controller won‘t work under auto mode.
Auto mode key and simulate auto key input does not work.
19
Reserved
20
Reserved