HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 56 of 69
Before system formal running, it is suggested to do following checks.
— Ensure all the connections are correct and wires diameter is suitable.
— Ensure that the controller DC power has fuse, controller‗s positive and negative connected to start
battery are correct.
— Emergency stop input is connected to positive of starter battery via the N/C point of emergency button
and the fuse.
— Take proper action to prevent engine to crank disconnect (e. g. Remove the connection wire of fuel
valve). If checking is OK, make the start battery power on; choose manual mode and controller will
execute routine.
— Set controller under manual mode, press ―start‖ button, genset will start. If start fails after pre-set start
attempts
, controller will send signal of Start Fail; then press ―stop‖ to reset controller.
— Recover the action of stopping engine start (e. g. Connect wire of fuel valve), press start button again,
genset will start. If everything goes well, genset will go to normal running after idle running (if idle run is
set). During this time, please observe
engine‘s running situations, AC generator‘s voltage and frequency
and DC generator voltage. If something abnormal occurs, stop genset running and check all wires
connection according to this manual.
— If there is any other question, please contact SmartGen‘s service.