HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 19 of 34
Num
Parameter
Range
Default
Remark
P 18
(P13)
Fail to stop
delay
(0-120)s
0
When
"ETS
solenoid
shutdown output time" for
zero, idle time delay stop
steady to time, and when
"ETS solenoid hold output
time" is not equal to zero,
from
ETS
solenoid
shutdown delay end to stop
steady need of time.
P 19
(P14)
ATS
close
time
(0-10)s
5.0
Mains or Genset switch
closing pulse width, when it
is
zero,
output
is
continuous.
P 20
(P15)
Flywheel teeth (10-300)
118
The
flywheel
teeth
on
engine starter teeth, used
for
starters
separation
condition
judgment
and
engine speed detection, see
behind
the
installation
instructions.
P 21
(P16)
Gens
abnormal
delay
(0-20.0)s
10.0
Too high or too low voltage
genset alarm delay.
P 22
(P17)
Gens over volt
shutdown
(30-360)V
264
When genset voltage is
over than the point, genset
over shutdown voltage is
active. When the point is
360V, genset over voltage is
disabled.
P 23
(P18)
Gens
under
volt
shutdown
(30-360)V
196
When genset voltage is
under than the point, genset
under shutdown voltage is
active. When the point is
30V, genset under voltage
is disabled.
P 24
(P19)
Under speed
shutdown
(0-6000)RPM
1200
When the engine speed is
under than the point and
hold great than 10 seconds,
genset
under
shutdown
speed is active.