HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 28 of 34
8 SETTING PARAMETER
After controller powered on, press
to enter into the parameters setting menu:
◙
Set parameters
When entering password, entering "1234" can set the item 1 to 47in the table
(parameters table [Table 1]), entering "0318" can set all items.
NOTE:
a
.
When the controller type is HGM6010KC, you will not have a table with a 1-5;
the programmable output 1-4 will have no power of some mains switch output.
b
.
Please modify the parameters (such as crank disconnect, input and output
configuration, various time, etc.) in standby mode, otherwise it might alarm
shutdown or other abnormal behavior.
c
.
The over-voltage threshold must be greater than the under-voltage threshold;
otherwise both will occur at the same time over-voltage and under-voltage
situation.
d
.
The over-speed threshold must be greater than under-speed threshold,
otherwise you will receive both the over speed and under speed.
e
.
As far as possible set the frequency (crank disconnect) to lower numerical, in
order to quickly crank disconnect when crank success.
f
.
Configurable input port 1-5 cannot set for the same items, otherwise cannot
appear correct function, configurable output 1-4 can be set for the same item.
g
.
If need to shutdown after cooling, please set any one configurable input as "
stop after cooling ", then connect this input with GND.
◙
Information
LCD will display the controller software version, issue date.
Note:
Press the key
will display the states of configurable input port and
output port state.
◙
Set language
User may set display interface language as Chinese, English and Spanish.
* Remark:
Press the key
will exit setting interface at any time.