HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 15 of 34
Pin
Function
Dim
Description
1
DC plant supply
input (-ve)
2.5mm
System DC negative input.
(Battery Negative).
2
DC plant supply
input (+ve)
2.5mm
System DC positive input.
(Battery Positive).
(Recommended Maximum Fuse 20A)
3
Emergency stop
input
2.5mm
Plant supply +ve. Also supplies fuel &
start outputs.
4
Fuel relay output
1.5mm
Plant ve from pin 3.
16 Amp rated.
5
Start relay output
1.5mm
Plant ve from
pin 3.
16 Amp rated.
Connect to
starter starting
coil.
6
Auxiliary output
relay 1
1.5mm
Plant ve from
pin 2.
7 Amp rated.
Reference
table 2
7
Auxiliary output
relay 2
1.5mm
Closed output,
7 Amp rated.
8
Relay common point
9
Open output,
7 Amp rated.
10 Auxiliary output
relay 3
2.5mm
Free volt contacts.
16 Amp rated
11
12 Auxiliary output
relay 4
2.5mm
13
14 Charge fail / excite 1.0mm Do not connect to ground (battery
–ve)