HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module ISSUE 2011-06-20 Version 1.7 Page 18 of 34
Num
Parameter
Range
Default
Remark
P 08
(P03)
Number
of
Crank
(1-10)Times
3
When
engine
start
no
success, most of cranking
numbers.
When
reach
setting
crank
numbers,
controller send out start fail
signal.
P 09
(P04)
Preheat time
(0-300)s
0
Before the starter adds the
electricity, preheat plug add
to the electricity in advance.
P 10
(P05)
Cranking time (3-60)s
8
The starter adds the time of
the electricity each time.
P 11
(P06)
Crank interval
time
(3-60)s
10
When the engine start not
successful, in the second
plus electric before the start
of the waiting time.
P 12
(P07)
Safe run time
(1-60)s
10
At
this
time,
low
oil
pressure,
high
water
temperature, under speed,
under
frequency,
under
voltage and charging failure
and
auxiliary
input
(configured) alarm is void
volume.
P 13
(P08)
Start idle time
(0-3600)s
0
Start genset idle running
time.
P 14
(P09)
Warming
up
time
(3-3600)s
10
Genset entered high speed
operation, in the warm-up
before closed for time.
P 15
(P10)
Cooling time
(3-3600)s
10
After unloading in genset,
the time needed to cool
before shutdown.
P 16
(P11)
Stop idle time
(0-3600)s
0
When stop idling genset
running time.
P 17
(P12)
ETS solenoid
hold
(0-120)s
20
It‟s the delay for energizing
to stop.