ALC700 Series Light Tower Set Controller
ALC700 Series Light Tower Set Controller 2018-03-02 Version 1.4 Page 42 of 51
8.7 OVER CURRENT ACTION
The formula of over current delay value:
T = t / ((IA/IT)-1)
2
T
:
Overcurrent delay (second)
t
:
Timing multiplier ratio
IA
:
Current max. load current
(
L1/L2/L3
)
IT
:
Overcurrent setting value
Example
:
t = 36
IA = 600A
IT =500A
Conclusion: T = 900s(15 minutes)
8.8 CONDITIONS OF CRANK DISCONNECT SELECTION
No.
Contents
0
Gen frequency (It is DC voltage when fitted with DC generator)
1 Speed sensor
2 Speed Gen frequency
3 Oil pressure
4 Oil pr Gen frequency
5 Oil pr Speed sensor
6 Oil pr Speed Gen frequency