ALC700 Series Light Tower Set Controller
ALC700 Series Light Tower Set Controller 2018-03-02 Version 1.4 Page 27 of 51
6.2 SHUTDOWN ALARMS
When controller detects shutdown alarm, it will send signal to turn off #1
~
#8 lights and shuts
down generator.
Shutdown alarms as following:
No.
Type
Description
1
Emergency Stop
When controller detects emergency stop signal, it will send a
shutdown signal and the corresponding alarm information will
be displayed on the LCD.
2
High Temp.
Shutdown
When controller detects the temperature is higher than the set
value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
3
Low OP Shutdown
When controller detects the oil pressure is lower than the set
value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
4
Over Speed
When controller detects the generator speed is higher than the
set value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
5
Under Speed
When controller detects the generator speed is lower than the
set value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
6
Loss of Speed
Signal
When controller detects the generator speed is 0, it will send a
shutdown signal and the corresponding alarm information will
be displayed on the LCD.
7
Over Frequency
When controller detects the generator frequency is higher than
the set value, it will send a shutdown signal and the
corresponding alarm information will be displayed on the LCD.
8
Under Frequency
When controller detects the generator frequency is lower than
the set value, it will send a shutdown signal and the
corresponding alarm information will be displayed on the LCD.
9
Over Voltage
When controller detects the generator voltage is higher than
the set value, it will send a shutdown signal and the
corresponding alarm information will be displayed on the LCD.
10
Under Voltage
When controller detects the generator voltage is lower than the
set value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
11
Over Current
When controller detects the current is higher than the set
value, it will send a shutdown signal and the corresponding
alarm information will be displayed on the LCD.
12
Fail To Start
If genset start failure within setting of start times, it will send a
shutdown signal and the corresponding alarm information will
be displayed on the LCD.