ALC700 Series Light Tower Set Controller
ALC700 Series Light Tower Set Controller 2018-03-02 Version 1.4 Page 16 of 51
C.
If generator voltage and frequency has reached on-load requirements (Voltage
≥ on-load
voltage and frequency
≥ on-load frequency), all the lights will illuminate in proper order and
the illumination interval delay is 2s (can be set as 1~300s). (Fig 5,6)
D.
When “Current Time” is 07:25:00(controller’s current time can be set via upper computer
software), then 1#
~
8# lights will off in proper order and the extinguishing interval delay
can be set as 1s
~
300s. The light tower set begin stopping when all the lights off. (Fig 7,8)
NOTE: The Sunrise/Sunset mode will be canceled automatically when select other auto
start mode
!
Fig 5
STOP DELAY 07:25:00
START TIME 17:26:00
CURRENT TIME 17:26:15
2# OUTPUT DELAY 09s
STOP DELAY 07:25:00
START TIME 17:26:00
CURRENT TIME 17:27:20
GENERATOR NORMAL RUNNING
Fig 6
Fig 7
STOP DELAY 07:25:00
START TIME 17:26:00
CURRENT TIME 07:25:00
7# OFF DELAY 09s
SUNRISE/SET ACTION
START TIME 17:26:00
CURRENT TIME 07:27:00
COOLING TIME 29s
Fig 8