![Smartgen ALC700 SERIES User Manual Download Page 30](http://html.mh-extra.com/html/smartgen/alc700-series/alc700-series_user-manual_1297472030.webp)
ALC700 Series Light Tower Set Controller
ALC700 Series Light Tower Set Controller 2018-03-02 Version 1.4 Page 30 of 51
7 WIRING CONNECTION
ALC700 controller’s rear as following:
Description of terminal connection:
NO.
Functions
Cable Size
Remark
1
DC input B-
2.5 mm
2
Connected with negative of starter
battery.
2
DC input B+
2.5 mm
2
Connected with positive of starter battery.
20A fuse is recommended.
3
Emergency stop
1.5 mm
2
Connected
with
DC
voltage
via
emergency stop button. Max. 30A fuse is
recommended.
4
Fuel relay
1.5 mm
2
DC voltage is supplied by 3 point, rated
8A.
5
Start Relay
1.5 mm
2
DC voltage is supplied by 3 point, rated
8A.
6
Aux. output 1
1.5 mm
2
B+ output
,
rated 8A.
7
Aux. output 2
1.5 mm
2
8
Aux. output 3
1.5 mm
2
9
Charger (D+)
1.0 mm
2
Connected with charger’s D+ (WL)
terminals. Ground connection is not
allowed.
10
Aux. output 4
1.5 mm
2
Normally open voltage free outputs, rated
8A.
11
1.5 mm
2
12
1#-4# COM
2.5 mm
2
Total output current: 8A
If 1~4 is all used, the maximum current of
each light is 2A.
13
1# Light Output
1.5 mm
2
14
2# Light Output
1.5 mm
2
15
3# Light Output
1.5 mm
2