9.3 HV120KL~200KLmode transfer to Maintain Bypass mode
Below is the step transfer to Maintain bypass mode:
1, if the UPS work in online mode, please turn off the UPS to bypass mode.
2, Removing the cover of the Maintain bypass, then the UPS will force transfer to bypass mode and
the warning 3A will alarm.
3, Close the Maintain bypass switch.
4, Turn off the Input Breaker and output breaker. If your UPS is Dual Input mode, please also turn off
the bypass breaker.