8.2.4.6 30-200K Major parameters of SPS section
。
30-200K SPS Section
Checked components
Instrument function
Reference
Value
Failed
Condition
F1,F2,F3,F4, F5, F6, F9, F10, F11, F12
Resistance
< 0.5 Ω
Open
D6,D13,D14,D7,D8,D10,D11,D12,D16,D17,D18,D19,D20,
D21,D22,D23,D24,D27
Diode Voltage Droop
»
0.59V
Short or open
D32,D35,D25,D26
Diode Voltage Droop
»
0.425V
Short or open
8.2.5 Output DC offset value test method
RC filter for test inverter offset (DC balance), check -50mV<output DC value < +50mV
9
How To Transfer the UPS from Online mode to Maintain Bypass mode
9.1 HV30KL/LV15KL mode transfer to Maintain Bypass mode
R
C
R
C
R=60K/5W, C=20uF/300V
L
N
Mul
Multimerter-