28
63
None
Inverter
L1
waveform
abnormal
the
voltage
difference
between
the
inverter
reference and inverter
sample is greater than
normal
Check the load is not overload and no surge
load ,Check the Inverter circuited
64
None
Inverter
L2
waveform
abnormal
the
voltage
difference
between
the
inverter
reference and inverter
sample is greater than
normal
65
None
Inverter
L3
waveform
abnormal
the
voltage
difference
between
the
inverter
reference and inverter
sample is greater than
normal
67
None
Bypass
output
short (L-N)
Bypass O/P voltage drop
too fast and O/P current
more than normal
Remove all the loads. Turn off the UPS.
Check
whether the output of UPS and loads are
short
circuited. Make sure the short circuit is
removed, and the UPS has no internal faults
before turning on again.
68
None
Bypass output line
short (L-L)
Each of line current more
than normal, but line plus
line current lower than
normal
Remove all the loads. Turn off the UPS.
Check
whether the output of UPS and loads are
short
circuited. Make sure the short circuit is
removed, and the UPS has no internal faults
before turning on again.
69
None
Inverter
Relay
short circuited
There isn’t signal drive the
Inverter Relay close, but
inverter output voltage over
normal
Check the Inverter Relay circuited
6C
None
BUS voltage vary
fast
BUS voltage drop too fast
in Inverter mode.
Remove all the loads. Turn off the UPS.
Check
whether the output of UPS and loads are
short
circuited.
6D
None
Current
detect
error
Inverter current and share
current and output current
sample deviation more
than normal
Check the current sample circuited on the
bypass board.
6E
None
SPS Power fault
SPS 12V power lower than
normal
Check the SPS circuited
6F
None
Battery
connect
reverse
Battery polarity reverse
Check the battery connect polarity
71
None
L1 PFC IGBT over
current fault
The unit have detected
IGBT fault signal from the
drive board
Check the IGBT drive signal and PFC IGBT
circuited
72
None
L2 PFC IGBT over
current fault
The unit have detected
IGBT fault signal from the
drive board
73
None
L3 PFC IGBT over
current fault
The unit have detected
IGBT fault signal from the
drive board
Summary of Contents for SBOL50KTIII-3
Page 2: ...2 ...
Page 10: ...10 n 5 Picture of the UPS 30k picture single input dual input ...
Page 11: ...11 30k UPS inner picture 60K picture ...
Page 12: ...12 60K picture 60K unit inner picture ...
Page 13: ...13 Front panel Rear panel Left panel 100K 200K picture ...
Page 14: ...14 Right side panel Top side panel 100K 200K picture ...
Page 38: ...38 HV30KL LV15KL Single Input Mode ...