Controller for single actuator (sideshift, tilt of yoke, telescopic arm)
(The illustration is from sideshift controller. The procedure is the same for tilt and telescoping)
No reaction on actuator for sideshift, tilt of
yoke or telescopic arm.
Voltage must be + 24 Volt
(Clamp 1 and 4)
Security switch can be abrupted
Voltage must be + 24 Volt between Clamps
1 and 6 as between 1 and 7
Fault on remote control when moving
single actuators
Voltage must be + 24 Volt between clamps
1 and 9 as between 1 and 10
Activate the control panel for movement
of tilt, sideshift or telescopic arm.
Voltage between clamps 2 and 3 must be
24 Volt or more
No reaction on movements and none of
the above faults.
Voltage between clamp 8 and 14 must be
+ 5 Volt
If this is not the case, the print on the
controller can be defective
Clamp 1 and 4
Clamp 1 and 6
Clamp 1 and 7
Clamp 1 and 9
Clamp 1 and 10
Clamp 2 and 3
Clamp 8 and 14