EUTECTIC EC-10 DV

5

If system pressure needs further control, add an additional tank or install a 
larger capacity tank. The automatic air vent should be installed in the top of 
the boiler, as in figure 3.

B. CONVENTIONAL COMPRESSION TANKS (non-diaphragm type) are used

to control system pressure in an AIR COLLECTING SYSTEM. Within the
system, after initial start-up and venting, air is collected in the tank and acts
in contact with the water to control pressure. Air is not vented from this sys-
tem. If system pressure needs further control, add another tank in parallel
with the original tank or install a large capacity tank. Locate the tank at the
inlet end of the pump near the boiler. (See figure 3)

C. HOT WATER RADIATION VENTING - Manual air vents should be installed

at the top of all "drops" (where piping goes downward). Air must be vented
or purged from all zone lines to permit proper system heating.

D. PUMP LOCATION - Locating low-head pump(s) on return to boiler is

acceptable for smaller boiler sizes in residences of one or two stories. The
pump location shown in figure 3 is required in large, multi-story building
installations, especially when high-head pumps are used.

IMPORTANT:

Hot water heating systems containing high water volume, such

as would occur with cast iron radiation, require special care with air elimina-
tion. The circulator pump should be located on the boiler supply pipe and the
expansion tank and air scoop should be located near the pump suction.

INSTALLING THE BURNER

See Burner Data, pages 9-10, and Burner Manual supplied with burner. If
burner is not mounted as received, mount to boiler, placing flange over
mounting studs. Use gasket between flange and boiler. Distance between
flange and nose of burner must be as shown on pages 9-10. Check to see
that nozzle and settings are as given in burner data tables, pages 9-10.

Figure 3.

Air Eliminating System or Alternating Collecting System. Pipe off to a safe place the relief valve and drain outlet.

Automatic

Air Vent

32mm 1-1/4"

NPT Supply

Air Eliminator as per

Manufacturer

Specifications

To Circ.(s)

and Zones

Supply Pipe

Mounted Tridicator

Relief Valve

19mm (3/4")

Panel Mounted

Tridicator

Temperature Sensor

Well

355mm

(13-31/32")

195mm

(7-11/16")

Panel Mounted

Tridicator

Pressure Sensor

Well

13mm (1/2") NPT

Tapping for Feed

Valve and Expansion

Tank

32mm (1-1/4") NPT

Return Tapping

Drain Outlet

WATER CONTENT OF BOILER

mm

in.

mm

in.

L/m

U.S.G/ft.

mm

in.

L/m

U.S.G/ft.

10

3/8

—     

11

0.430

0.093

0.0075

13

1/2

40

16

0.622

0.195

0.0157

14

0.545

.0150

0.0121

16

5/8

—  

17

0.666

0.225

0.0181

19

3/4

40

21

0.824

0.344

0.0277

20

0.785

0.311

0.0251

25

1

40

27

1.049

0.557

0.0449

26

1.025

0.532

0.0429

32

1

1

/

4

40

35

1.380

0.967

0.0779

32

1.265

0.810

0.0653

38

1

1

/

2

40

41

1.610

1.315

0.106

38

1.505

1.147

0.0924

51

2

40

53

2.067

2.159

0.174

50

1.985

1.998

0.161

64

2

1

/

2

40

63

2.469

3.090

0.249

63

2.465

3.078

0.248

76

3

40

78

3.068

4.765

0.384

75

2.945

4.393

0.354

Nominal 

Pipe Size 

Schedule

No.

Inside

Diameter

Volume per

linear unit.

Inside

Diameter

Volume per

linear unit.

Standard Steel Pipe

Type L Copper Tube

VOLUME OF WATER IN STANDARD PIPE OR TUBE

EC-13

EC-14

EC-15

EC-16

L

USG

L

USG

L

USG

L

USG

18.9

5

24.6

6.5

30.3

8

36.1

9.5

Summary of Contents for EUTECTICEC-15DV

Page 1: ...the more stringent require ment shall govern In addition where required by the authority having juris diction the installation must conform to American Society of Mechanical Engineers Safety Code for...

Page 2: ...Department of Energy D O E Test Procedures for Boil ers TABLE 1 Ratings and Dimensions Figure 1 Dimensions Boiler Model No OIL INPUT GROSS OUTPUT NET OUT PUT DIMENSIONS APPROX OVERALL LENGTH A BOILER...

Page 3: ...minate vent under decks stairways or car ports When ever possible locations under windows should be avoided Vent termination should not be mounted directly above or within 914mm 3 feet horizontally fr...

Page 4: ...be left clear around the boiler Do not stack items on or box in the appliance within the required clearances to combustibles The figures stated in metric inches in the drawing below are the minimum re...

Page 5: ...See Burner Data pages 9 10 and Burner Manual supplied with burner If burner is not mounted as received mount to boiler placing flange over mounting studs Use gasket between flange and boiler Distance...

Page 6: ...and air supply pipe are properly installed and clear of obstruction Note Neither overfire nor flue draft should exceed 8 9mm 0 35 WC during burner operation THE FLUE IS UNDER POSITIVE PRESSURE DURING...

Page 7: ...EUTECTIC EC 10 DV 7 Honeywell L7248L Control...

Page 8: ...EUTECTIC EC 10 DV 8 Honeywell L7248L with SF 10 Control...

Page 9: ...of interest For example press I High Limit HL is displayed followed by a three digit number i e 220 followed by F or C Pressing the I button again on L7224 models will display the Low Limit LL followe...

Page 10: ...2 4 2 none 107 95 4 25 EUTECTIC EC 10 DV 10 Models BF 3 BF 5 Electrode Setting Turbulator location Picture 1 TURBULATOR SETTING 1 Loosen nut 1 then turn the screw 2 until the index marker 3 is aligne...

Page 11: ...r to increase combustion air turn the screw clockwise indicator to decrease combustion air 3 The final position of the air damper will vary on each installation Use instruments to establish the proper...

Page 12: ...oped in the combustion chamber Vacuum the loose soot and debris from the boiler Clean and replace baffle plates Inspect the burner combustion head Clean if necessary and make sure all the adjustments...

Page 13: ...approximately 54 degrees Celsius 130 degrees Fahrenheit most of the flow will be through the system Mounting TV can be installed in any position An adjustable balancing valve or ball valve must be ins...

Page 14: ...d by local codes If the boiler is installed above the radiation level a low water cut off device must be installed in all instances Do not install an isolation valve between the boiler and the low wat...

Page 15: ...er hinges 2 You may have to loosen the cast iron hinge pin 3 to facilitate removal of the lower hinge 3 Remove the cast iron hinge pin 3 which is attached by two 13 mm bolts 4 4 Re install the two bol...

Page 16: ...Fin Corp 2008 SLANT FIN LTD LTEE 6450 Northam Drive Mississauga Ontario L4V 1H9 Phone 905 677 8400 FAX 905 677 1829 Order Desk Fax 905 677 9015 www slantcan ca E mail orderdesk slantfin ca info slant...

Reviews: