background image

6

EUTECTIC EC-10 DV

CAUTION:

DO NOT USE GASOLINE, CRANKCASE

DRAININGS, OR ANY OIL CONTAINING GASOLINE.

OIL SUPPLY PIPING

Install the oil tank or tanks and piping from tank to burner. Follow local codes
and practices, NFPA No. 31, INSTALLATION OF OIL BURNING EQUIPMENT
and the instruction sheet attached to the oil burner pump. A one-pipe system
should be used for gravity fed fuel systems and for lift systems, where the
total lift is less than 8 ft. Where the total lift is greater than 8 ft., a two-pipe sys-
tem must be used. In some instances, local codes may require a two-pipe
system for below grade fuel oil tanks. Be sure to set-up the fuel oil pump for
the piping system used; follow the instructions attached to the pump. Be
sure to include a good quality, low pressure drop fuel oil filter in the supply
line from the tank. This is necessary, especially at low fuel oil flow rates
(small nozzle sizes), to prevent nozzle plugging.

WIRING THE BOILER

• The wiring diagrams for the burner and boiler may be found on pages 6-7.
• 24 volt control wiring should be approved Safety Circuit wire, protected 

as needed.

• Power supply wiring to the burner must be 14 gauge or heavier, as 

required, and should have a properly fused disconnect switch. 120 volt 
wiring to pumps and safety controls must also be 14 gauge or heavier. 
Wire must be enclosed in approved conduit.

•  All wiring must be installed in compliance with the National Electric 

Code, or any local or insurance codes having jurisdiction.

Wiring to the boiler must come through an emergency power
isolation switch with a clearly marked red switch plate. This
switch should be located so that it is apparent to the home-
owner when entering the basement or other boiler area. The
homeowner should be made familiar with operating the toggle
to provide or stop the power to the boiler.

PRECAUTIONS BEFORE STARTING OIL BURNER

Make a positive check of A through I before starting burner:
A. Boiler and system are full of water. All air is vented from system. 

See below.

B. All wiring is completed. See pages 7-8.
C. Oil supply is connected to the burner; nozzle is installed correctly; oil 

valve is open at tank.

D. All combustible materials are cleared away.
E. All vent piping is properly installed and sealed.
F. Burner settings are adjusted as per pages 9 & 10 and as shown on 

boiler jacket label.

G. Main cast iron door on which burner is mounted is bolted shut and 

fiberglass rope seal is making good contact.

H. Make sure boiler has correct quantity of baffles (see top of pag 3).
I.

Make sure vent pipe, vent terminal and air supply pipe are properly 
installed and clear of obstruction.

Note: Neither overfire nor flue draft should exceed

8.9mm (0.35") WC during burner operation

THE FLUE IS UNDER POSITIVE PRESSURE DURING

 OPERATION. ALL VENTING MUST BE SEALED AND

CHECKED ON A REGULAR INTERVAL.

OPERATING INSTRUCTIONS

CLEANING AND FILLING A NEW WATER BOILER

I.   BEFORE FILLING WATER BOILER

A.

Check burner to be certain it is ready for firing. DO NOT FIRE 
into an empty boiler.

B.

Be prepared to heat raw water to at least 82°C (180°F) as soon as it is
introduced into the boiler. This procedure will remove dissolved,
 corrosive gases.

C. Provide drain line, with valve, from boiler. Use a bottom tapping. 

Line and drain must be suitable for handling caustic solution.

II.  CLEANING WATER BOILER SYSTEM

A.

Use a commercial cleaning solution, such as 

Rhomar Hydro-Solv 

9100 Cleaner 

as directed in product instructions.

B.

Use a commercial treatment solution, such as 

Rhomar Pro-Tek 922 

Treatment

as directed in product instructions.

III. FILLING AND VENTING THE WATER BOILER

A.

Refill the system with fresh water.

B.

Bring water temperature to at least 82°C (180°F) promptly.

C. Circulate water through entire system.
D. Vent the system, including the radiation.
E. The boiler is now ready to be put into service or on standby.
F.

If brand-name air-control devices are used, venting instructions
 furnished with the devices should be followed.

IV. SAFETY CHECK FOR CONTROL SYSTEM

High limit control test: Set thermostat high enough for boiler water 
temperature to reach high limit control setting. When this temperature is 
reached, the high limit switch should open, and the burner should shut off 
automatically. If the high limit does not operate to shut off the burner, the 
high limit or the wiring is faulty. Repair or replace immediately.

START-UP

(COMBUSTION TEST INSTRUMENTS MUST

BE USED) 

THIS BOILER IS A POSITIVE PRESSURE BOILER

.

A. Make sure the boiler is installed and wired properly and is full

of water.

B. The observation port cover is mounted on the hinged burner

mounting door. NEVER touch the port cover or any surrounding
surfaces with hands. They may be HOT. Use tools. Loosen the
screw and swing cover to be able to insert probe through slot,
when necessary. See the burner instructions for bleeding air, etc.

C. Take a smoke reading soon after starting burner. If smoke is not 

zero or trace, open air to clear smoke and let burner fire.

D. DO NOT ATTEMPT TO SET FIRE BY EYE. A smoke gun and a

combustion analyzer must be used. Adjust the air to get approxi-
mately 12% CO

2

with a zero or trace smoke. Then check and

record draft and flue temperature.

E. Make sure that the observation port cover is closed tight, the

burner is secure. Turn burner on and off at least 3 times to
check ignition.

Summary of Contents for EUTECTICEC-15DV

Page 1: ...the more stringent require ment shall govern In addition where required by the authority having juris diction the installation must conform to American Society of Mechanical Engineers Safety Code for...

Page 2: ...Department of Energy D O E Test Procedures for Boil ers TABLE 1 Ratings and Dimensions Figure 1 Dimensions Boiler Model No OIL INPUT GROSS OUTPUT NET OUT PUT DIMENSIONS APPROX OVERALL LENGTH A BOILER...

Page 3: ...minate vent under decks stairways or car ports When ever possible locations under windows should be avoided Vent termination should not be mounted directly above or within 914mm 3 feet horizontally fr...

Page 4: ...be left clear around the boiler Do not stack items on or box in the appliance within the required clearances to combustibles The figures stated in metric inches in the drawing below are the minimum re...

Page 5: ...See Burner Data pages 9 10 and Burner Manual supplied with burner If burner is not mounted as received mount to boiler placing flange over mounting studs Use gasket between flange and boiler Distance...

Page 6: ...and air supply pipe are properly installed and clear of obstruction Note Neither overfire nor flue draft should exceed 8 9mm 0 35 WC during burner operation THE FLUE IS UNDER POSITIVE PRESSURE DURING...

Page 7: ...EUTECTIC EC 10 DV 7 Honeywell L7248L Control...

Page 8: ...EUTECTIC EC 10 DV 8 Honeywell L7248L with SF 10 Control...

Page 9: ...of interest For example press I High Limit HL is displayed followed by a three digit number i e 220 followed by F or C Pressing the I button again on L7224 models will display the Low Limit LL followe...

Page 10: ...2 4 2 none 107 95 4 25 EUTECTIC EC 10 DV 10 Models BF 3 BF 5 Electrode Setting Turbulator location Picture 1 TURBULATOR SETTING 1 Loosen nut 1 then turn the screw 2 until the index marker 3 is aligne...

Page 11: ...r to increase combustion air turn the screw clockwise indicator to decrease combustion air 3 The final position of the air damper will vary on each installation Use instruments to establish the proper...

Page 12: ...oped in the combustion chamber Vacuum the loose soot and debris from the boiler Clean and replace baffle plates Inspect the burner combustion head Clean if necessary and make sure all the adjustments...

Page 13: ...approximately 54 degrees Celsius 130 degrees Fahrenheit most of the flow will be through the system Mounting TV can be installed in any position An adjustable balancing valve or ball valve must be ins...

Page 14: ...d by local codes If the boiler is installed above the radiation level a low water cut off device must be installed in all instances Do not install an isolation valve between the boiler and the low wat...

Page 15: ...er hinges 2 You may have to loosen the cast iron hinge pin 3 to facilitate removal of the lower hinge 3 Remove the cast iron hinge pin 3 which is attached by two 13 mm bolts 4 4 Re install the two bol...

Page 16: ...Fin Corp 2008 SLANT FIN LTD LTEE 6450 Northam Drive Mississauga Ontario L4V 1H9 Phone 905 677 8400 FAX 905 677 1829 Order Desk Fax 905 677 9015 www slantcan ca E mail orderdesk slantfin ca info slant...

Reviews: