9

EUTECTIC EC-10 DV

ADJUSTING SETTINGS

To discourage unauthorized changing of Aquastat settings, a procedure
to enter the ADJUSTMENT mode is required. To enter the ADJUSTMENT
mode, press the UP, DOWN, and I buttons simultaneously for three sec-
onds. Press the I button until the feature requiring adjustment is dis-
played:

. HL_ . High Limit.
. LL_ . Low Limit. (L7224 only)
. Ldf . Low Limit Differential. (L7224 only)
. °F . °C.
.ELL_ External Low Limit (L7248L only)

Then press the UP and/or DOWN buttons to move the set point to the
desired value, to change between ÞF and CÞ, or to enable (On) or dis-
able (Off) the External Low Limit. After 60 seconds without any button
inputs, the control will automatically return to the RUN mode.

DISPLAY

In the RUN mode, the Aquastat will flash .bt. (boiler temp) followed by the
temperature (i.e., 220), followed by °F or °C.

To read boiler settings, press the I key to read the parameter of interest.
For example, press I High Limit
(HL) is displayed, followed by a three-digit number, i.e., 220, followed by

°F or °C. Pressing the I button again (on L7224 models) will display the
Low Limit (LL) followed by a three-digit number and the corresponding
degree designator. 

After approximately 60 seconds without any key presses, the display will
enter a dim display mode. To return to the bright display mode, simply
press any key. 

DESCRIPTION

Boiler Temperature – 

High Limit –

Low Limit –

Low Limit Differential –

Local Thermostat Status –

Enviracom Thermostat Status –

Error Code –

Degrees Fahrenheit –

Degrees Celsius –

Error Code

Cause/Action

Err1

Sensor fault; check sensor.

Err2

ECOM fault; check EnviraCOM

wiring

Err3

Hardware fault; replace control.

Err4

B1 fault; check B1 wiring/voltage.

Err5

Low Line; Check L1-L2, 110 Vac.

Err6

Fuse; Check ECOM wires, replace fuse.

Err7

EEPROM, HL, LL, Hdf, Ldf: reset to 

deault values. Restore desired settings.

Err8

Repeated B1 fault (no voltage present
at B1 when output is turned on water
temperature above 260F when voltage
present at B1); check B1 wiring/voltage.

FOR  L7248L

Summary of Contents for EUTECTICEC-15DV

Page 1: ...the more stringent require ment shall govern In addition where required by the authority having juris diction the installation must conform to American Society of Mechanical Engineers Safety Code for...

Page 2: ...Department of Energy D O E Test Procedures for Boil ers TABLE 1 Ratings and Dimensions Figure 1 Dimensions Boiler Model No OIL INPUT GROSS OUTPUT NET OUT PUT DIMENSIONS APPROX OVERALL LENGTH A BOILER...

Page 3: ...minate vent under decks stairways or car ports When ever possible locations under windows should be avoided Vent termination should not be mounted directly above or within 914mm 3 feet horizontally fr...

Page 4: ...be left clear around the boiler Do not stack items on or box in the appliance within the required clearances to combustibles The figures stated in metric inches in the drawing below are the minimum re...

Page 5: ...See Burner Data pages 9 10 and Burner Manual supplied with burner If burner is not mounted as received mount to boiler placing flange over mounting studs Use gasket between flange and boiler Distance...

Page 6: ...and air supply pipe are properly installed and clear of obstruction Note Neither overfire nor flue draft should exceed 8 9mm 0 35 WC during burner operation THE FLUE IS UNDER POSITIVE PRESSURE DURING...

Page 7: ...EUTECTIC EC 10 DV 7 Honeywell L7248L Control...

Page 8: ...EUTECTIC EC 10 DV 8 Honeywell L7248L with SF 10 Control...

Page 9: ...of interest For example press I High Limit HL is displayed followed by a three digit number i e 220 followed by F or C Pressing the I button again on L7224 models will display the Low Limit LL followe...

Page 10: ...2 4 2 none 107 95 4 25 EUTECTIC EC 10 DV 10 Models BF 3 BF 5 Electrode Setting Turbulator location Picture 1 TURBULATOR SETTING 1 Loosen nut 1 then turn the screw 2 until the index marker 3 is aligne...

Page 11: ...r to increase combustion air turn the screw clockwise indicator to decrease combustion air 3 The final position of the air damper will vary on each installation Use instruments to establish the proper...

Page 12: ...oped in the combustion chamber Vacuum the loose soot and debris from the boiler Clean and replace baffle plates Inspect the burner combustion head Clean if necessary and make sure all the adjustments...

Page 13: ...approximately 54 degrees Celsius 130 degrees Fahrenheit most of the flow will be through the system Mounting TV can be installed in any position An adjustable balancing valve or ball valve must be ins...

Page 14: ...d by local codes If the boiler is installed above the radiation level a low water cut off device must be installed in all instances Do not install an isolation valve between the boiler and the low wat...

Page 15: ...er hinges 2 You may have to loosen the cast iron hinge pin 3 to facilitate removal of the lower hinge 3 Remove the cast iron hinge pin 3 which is attached by two 13 mm bolts 4 4 Re install the two bol...

Page 16: ...Fin Corp 2008 SLANT FIN LTD LTEE 6450 Northam Drive Mississauga Ontario L4V 1H9 Phone 905 677 8400 FAX 905 677 1829 Order Desk Fax 905 677 9015 www slantcan ca E mail orderdesk slantfin ca info slant...

Reviews: