background image

13

EUTECTIC EC-10 DV

APPENDIX A

THERMOSTATIC BYPASS VALVE

TYPICAL MOUNTING

TYPICAL RETURN VALVE MOUNTING

TO SYSTEM

FROM SYSTEM

BOILER

SIZE

25 mm (1") NPT (female x female)
32 mm (1-1/4") NPT (female x female)
38 mm (1-1/2") NPT (female x female)

S/F PART NO.

116040
116041
116042

OPEN TEMP.

46 ºC

115 ºF

46 ºC

115 ºF

46 ºC

115 ºF

A

107 mm 4.2"
114 mm 4.5"
119 mm 4.7"

A/2

53 mm 2.1"
57 mm 2.25"

60 mm 2.

35"

Cv

10.5
16.4
20.2

Kv

8.96

13.99
17.23

WEIGHT

1.5 kg

3.3 lb

2.0 kg

4.4 lb

2.4 kg

5.3 lb

Max. operating pressure 6 bar (85 psi) Maximum operating temperature 110°C (230°F)

The flow factor Kv is the number of cubic meters per hour of water at 20°C which will flow through the valve with a pressure drop of 1kg/cm

2

(1 bar).

The flow coefficient Cv is the flow of water at 60°F in US gallons per minute at a pressure drop of 1lb/in

2

across the valve.

Thermostatic bypass valves type TV are designed to allow
boilers to reach their optimum operating temperature 
quickly and to prevent cool/cold return temperatures from
affecting them.

Operation/Installation: The thermostat within the "TV" valve
allows full flow through the bypass until the predetermined
temperature is reached.

Start Up: With the balancing valve on the bypass fully 
open, operate the boiler until it reaches its normal 
operating temperature. If hot water does not automatically
flow to the system then adjust (throttle) the bypass 
balancing valve until flow (hot water) to the system is

established. If flow is already to the system, no adjustment 
is required.

When mounted on the return "TV" allows full bypass until the
return temperature reaches 46 degrees Celsius (115 degrees
Fahrenheit). "TV" will begin opening while main taining a 46
degrees Celsius (115 degrees Fahrenheit) minimum return
temperature. When return temperatures reach approximately
54 degrees Celsius (130 degrees Fahrenheit) most of the flow
will be through the system.

Mounting: "TV" can be installed in any position. An adjust able
balancing valve (or ball valve) must be installed on 
the bypass.

APPENDIX B

THERMOSTAT HEAT ANTICAPATOR SETTINGS

Fixed anticipator thermostats are not adjustable.

Adjustable anticipator thermostats, depending on thermostat
model, may be adjustable from a .18 to a .9 setting by moving
a pointer on the anticipator.

The higher the anticipator setting (towards .9) the longer it 
will take for the thermostat to respond to a change in room
temperature. Too high a setting and the boiler will be slow to
respond to a temperature change in the room. This can 
cause the room temperature to drop to an uncomfortable
level before the boiler starts. This may generate homeowner
complaints.

The lower the anticipator setting (toward .18) the faster the
thermostat will respond to a change in room temperature. Too
low a setting and the boiler will short cycle. Boiler short
cycling will cause unnecessary wear on the equipment and in
the case of oil boilers it can lead to poor combustion and
more frequent cleaning of the combustion area.

It is important to understand what the thermostat is controlling
and then determine the amp rating of that relay, gas valve,
zone valve or control. This information is usually stamped
somewhere on the component. A properly set  anticipator will
allow the system to operate at its maximum effectiveness.

APPENDIX C

USE OF NON-OXYGEN DIFFUSION BARRIER UNDERFLOOR TUBING

The boiler warranty does not cover leaks resulting from
corrosion caused by the use of underfloor plastic tubing
without an oxygen diffusion barrier. Systems must have the
non-oxygen diffusion barrier tubing separated from the boiler

with a heat exchanger, Slant/Fin recommends the use of
underfloor plastic tubing with an oxygen diffusion barrier.
Other system components may also require protection from
oxygen permeation.

Summary of Contents for EUTECTICEC-15DV

Page 1: ...the more stringent require ment shall govern In addition where required by the authority having juris diction the installation must conform to American Society of Mechanical Engineers Safety Code for...

Page 2: ...Department of Energy D O E Test Procedures for Boil ers TABLE 1 Ratings and Dimensions Figure 1 Dimensions Boiler Model No OIL INPUT GROSS OUTPUT NET OUT PUT DIMENSIONS APPROX OVERALL LENGTH A BOILER...

Page 3: ...minate vent under decks stairways or car ports When ever possible locations under windows should be avoided Vent termination should not be mounted directly above or within 914mm 3 feet horizontally fr...

Page 4: ...be left clear around the boiler Do not stack items on or box in the appliance within the required clearances to combustibles The figures stated in metric inches in the drawing below are the minimum re...

Page 5: ...See Burner Data pages 9 10 and Burner Manual supplied with burner If burner is not mounted as received mount to boiler placing flange over mounting studs Use gasket between flange and boiler Distance...

Page 6: ...and air supply pipe are properly installed and clear of obstruction Note Neither overfire nor flue draft should exceed 8 9mm 0 35 WC during burner operation THE FLUE IS UNDER POSITIVE PRESSURE DURING...

Page 7: ...EUTECTIC EC 10 DV 7 Honeywell L7248L Control...

Page 8: ...EUTECTIC EC 10 DV 8 Honeywell L7248L with SF 10 Control...

Page 9: ...of interest For example press I High Limit HL is displayed followed by a three digit number i e 220 followed by F or C Pressing the I button again on L7224 models will display the Low Limit LL followe...

Page 10: ...2 4 2 none 107 95 4 25 EUTECTIC EC 10 DV 10 Models BF 3 BF 5 Electrode Setting Turbulator location Picture 1 TURBULATOR SETTING 1 Loosen nut 1 then turn the screw 2 until the index marker 3 is aligne...

Page 11: ...r to increase combustion air turn the screw clockwise indicator to decrease combustion air 3 The final position of the air damper will vary on each installation Use instruments to establish the proper...

Page 12: ...oped in the combustion chamber Vacuum the loose soot and debris from the boiler Clean and replace baffle plates Inspect the burner combustion head Clean if necessary and make sure all the adjustments...

Page 13: ...approximately 54 degrees Celsius 130 degrees Fahrenheit most of the flow will be through the system Mounting TV can be installed in any position An adjustable balancing valve or ball valve must be ins...

Page 14: ...d by local codes If the boiler is installed above the radiation level a low water cut off device must be installed in all instances Do not install an isolation valve between the boiler and the low wat...

Page 15: ...er hinges 2 You may have to loosen the cast iron hinge pin 3 to facilitate removal of the lower hinge 3 Remove the cast iron hinge pin 3 which is attached by two 13 mm bolts 4 4 Re install the two bol...

Page 16: ...Fin Corp 2008 SLANT FIN LTD LTEE 6450 Northam Drive Mississauga Ontario L4V 1H9 Phone 905 677 8400 FAX 905 677 1829 Order Desk Fax 905 677 9015 www slantcan ca E mail orderdesk slantfin ca info slant...

Reviews: