background image

EUTECTIC EC-10 DV

12

CARE AND MAINTENANCE

I. EXTENDED SHUTDOWN, CLEANING OR REMOVAL OF

BOILER FROM SERVICE.
DANGER: Use CAUTION when handling chemicals and
draining hot water from a boiler. Scalding water and/or
chemicals can cause permanent injury to the skin, eyes and
respiratory system.
A.

Shut down burner by disconnecting all electrical power
to the burner by turning OFF the BURNER
EMERGENCY SWITCH of this boiler. After shutting
down burner, while the boiler is still hot [82°C to 93°C
(180°F to 200°F)], drain water from the bottom of the
boiler until it runs clear.

B.

Provide corrosion protection conditioning to the boiler
water in the heating system. There are a number of
commercial heating system preparations available from
your distributor. Follow the preparation manufacturer’s
instructions.

II CLEANING OF BOILER
1. To clean the fireside boiler surfaces, first shut down burner

by disconnecting all electrical power to the burner by
turning OFF the OIL BURNER EMERGENCY SWITCH of this
boiler in order to perform the following in (a) through (h)
below.
a.

Remove the flue pipe from the boiler flue collar clean
thoroughly.

b.

Inspect the entire vent connector back to the chimney
and clean if necessary.

c.

Inspect the chimney for soot, debris and other unsafe
conditions of the chimney and take the necessary
action.

d.

Remove the boiler jacket front panel to open burner
door as follows:
1. Lift the window. 
2. Unscrew the two front panel side attachment screws. 
3. Unclip the front panel from the clips and notches

near the top, and pull it towards you.

4. Remove the front panel from the notches in the

bottom of the side panels.

e.

The burner mounting door must be fully open to clean
the flue passages and the combustion chamber. If the
oil line is not flexible enough it should be disconnected
from the burner during the cleaning process. The
flexible electric conduit connected from the junction
box on the boiler to the burner via a plastic connector
must be disconnected from the burner by grasping the
plastic half of the connector closest to the flexible
conduit and gently pulling it in the direction of the
conduit until it is disconnected. Remove all four 13 mm
hex head screws on the sides of the swinging door.
You will need a 13 mm open end or box wrench. Open
the door to completely expose the combustion
chamber for thorough cleaning and for inspection of
main cast iron burner door insulation and burner door
fiberglass sealing rope .If combustion chamber parts
above are badly deteriorated then replace with original
factory parts available at your distributor. 

f.

Use the flue brush to clean the flue passages and
combustion chamber. 
Remove cast iron baffle plates for cleaning [2 baffle
plates in ECDV-13 to 0 baffle plates in ECDV14, 15 &
16]. A wire brush may be used to remove any carbon
accumulation that may have developed in the
combustion chamber. Vacuum the loose soot and
debris from the boiler. Clean and replace baffle plates.
Inspect the burner combustion head. Clean if
necessary and make sure all the adjustments are
correct (See burner data pages for the burner
installed). Replace oil nozzle with the new one and re-
adjust electrodes. To insure proper burner operation

ONLY THE NOZZLES SPECIFIED IN THIS MANUAL OR
ON THE BURNER LABEL SHOULD BE USED FOR
REPLACEMENT.

g.

Close main cast-iron burner door (door on which
burner is mounted). Make sure that the entire seal
(fiberglass rope) is making good contact with the boiler
casting when replacing the four 13 mm hex head
screws and tightening.

h.

Replace boiler jacket front panel. 

2. If boiler room is damp, provide ventilation.

CAUTION:

ALWAYS KEEP THE OIL SUPPLY VALVE SHUT OFF

IF THE BURNER IS SHUT DOWN FOR AN EXTENDED PERI-
OD OF TIME

II. PROVIDING PROTECTION FOR FREEZING

Anti-freeze is sometimes used in hydronic heating systems
to protect against freeze-up in the event of power failure, or
safety control shutdown when the building is unoccupied. It
should be recognized that unless the building is kept above
freezing temperature by some means, the plumbing system
is not protected.

PROPYLENE GLYCOL is used in the quick-freeze food
industry; it is practically non-toxic. Its use may be permitted
when indirect water heaters are used. When anti-freeze must
be used, inhibited propylene glycol is recommended. Useful
information on the characteristics, mixing propor tions, etc. of
glycol in heating systems is given in Technical Topics No.
2A, available from the Hydronics Division of GAMA, 35
Russo Place, Berkeley Heights, NJ 07922. Consult glycol
manufacturers for sources of propylene glycol.

DO NOT USE ETHYLENE GLYCOL BECAUSE IT IS TOXIC.

III. OIL BURNER

All service to the oil burner, oil filter, oil strainer, etc., should
be performed by a professionally trained service person.
Inspect and clean annually and following any period of
improper operation. Recheck and adjust settings as
specified for burner model and nozzle size. 
Set burner air using test instruments to obtain recommend -
ed CO2 and draft without smoke. See the Burner Data page
in this manual that corresponds to the burner installed.

IV. GENERAL MAINTENANCE

These operations are recommended to be performed at
regular intervals:
A.

BOILER HEATING SURFACES: clean off all coatings
found. Reseal covers.

B.

BOILER CONTROLS: check settings, correct
functioning.

C.

PIPING: check piping and accessories for leaks.

D.

STUB VENT and BREECHING: check for obstructions
and leaks.

E.

COMBUSTION AIR TO BURNER: check for continued
POSITIVE supply of air as required. Air needs are
greatest in coldest weather. Refer to AIR SUPPLY,
page 3.

F.

WATER SYSTEM: check
1.

System to be full of water and pressure to remain
stable (between 83 kPa and 172 kPa [12 psi and
25 psi]).

2.

Air-control system: noise and air binding in
radiation should not occur.

3.

Water lines: slightest leaks should be corrected.

G.

BOILER ROOM AIR SUPPLY: air vents should be open
and free of obstruction.

Summary of Contents for EUTECTICEC-15DV

Page 1: ...the more stringent require ment shall govern In addition where required by the authority having juris diction the installation must conform to American Society of Mechanical Engineers Safety Code for...

Page 2: ...Department of Energy D O E Test Procedures for Boil ers TABLE 1 Ratings and Dimensions Figure 1 Dimensions Boiler Model No OIL INPUT GROSS OUTPUT NET OUT PUT DIMENSIONS APPROX OVERALL LENGTH A BOILER...

Page 3: ...minate vent under decks stairways or car ports When ever possible locations under windows should be avoided Vent termination should not be mounted directly above or within 914mm 3 feet horizontally fr...

Page 4: ...be left clear around the boiler Do not stack items on or box in the appliance within the required clearances to combustibles The figures stated in metric inches in the drawing below are the minimum re...

Page 5: ...See Burner Data pages 9 10 and Burner Manual supplied with burner If burner is not mounted as received mount to boiler placing flange over mounting studs Use gasket between flange and boiler Distance...

Page 6: ...and air supply pipe are properly installed and clear of obstruction Note Neither overfire nor flue draft should exceed 8 9mm 0 35 WC during burner operation THE FLUE IS UNDER POSITIVE PRESSURE DURING...

Page 7: ...EUTECTIC EC 10 DV 7 Honeywell L7248L Control...

Page 8: ...EUTECTIC EC 10 DV 8 Honeywell L7248L with SF 10 Control...

Page 9: ...of interest For example press I High Limit HL is displayed followed by a three digit number i e 220 followed by F or C Pressing the I button again on L7224 models will display the Low Limit LL followe...

Page 10: ...2 4 2 none 107 95 4 25 EUTECTIC EC 10 DV 10 Models BF 3 BF 5 Electrode Setting Turbulator location Picture 1 TURBULATOR SETTING 1 Loosen nut 1 then turn the screw 2 until the index marker 3 is aligne...

Page 11: ...r to increase combustion air turn the screw clockwise indicator to decrease combustion air 3 The final position of the air damper will vary on each installation Use instruments to establish the proper...

Page 12: ...oped in the combustion chamber Vacuum the loose soot and debris from the boiler Clean and replace baffle plates Inspect the burner combustion head Clean if necessary and make sure all the adjustments...

Page 13: ...approximately 54 degrees Celsius 130 degrees Fahrenheit most of the flow will be through the system Mounting TV can be installed in any position An adjustable balancing valve or ball valve must be ins...

Page 14: ...d by local codes If the boiler is installed above the radiation level a low water cut off device must be installed in all instances Do not install an isolation valve between the boiler and the low wat...

Page 15: ...er hinges 2 You may have to loosen the cast iron hinge pin 3 to facilitate removal of the lower hinge 3 Remove the cast iron hinge pin 3 which is attached by two 13 mm bolts 4 4 Re install the two bol...

Page 16: ...Fin Corp 2008 SLANT FIN LTD LTEE 6450 Northam Drive Mississauga Ontario L4V 1H9 Phone 905 677 8400 FAX 905 677 1829 Order Desk Fax 905 677 9015 www slantcan ca E mail orderdesk slantfin ca info slant...

Reviews: