DOL 535 • DOL 539
8
Technical Manual
3 Installation guide
3.1 Selecting components
There are two ways to carry out installation of the controller.
At the initial installation:
Use Installation wizard which will guide you through all the options of the functions.
At adaptation of the existing installation:
Use the menu
Technical | Manual installation
which enables you
to go directly to the relevant function.
Select components in the installation menu of the controller.
(
Technical | Installation | Start installation
or
Manual
installation
).
It is not possible to select more components than there is avail-
able I/O for.
You must therefore be aware of whether the controller accepts
your wish to connect a component
If missing I/O, you can:
• install extra I/O modules (if these are available).
• uninstall components.
While functions are selected in the
Installation
and
Show con-
nections
setup menus, all alarms will be delayed. Thus, no
alarms will be generated until 2 minutes after the last change in
the installation menu.
This is indicated as info in the alarm menu for as long as the
delay is active.
This does not apply to alarms from CAN bus communication (I/
O modules).
3.2 Select type of unit of measurements
Unit of measurements
The controller and display units as either metric or US units.
3.3 View week number
Show week number
View of week number at the top of all pages.
3.4 Connecting Components
The main part of the connection terminals is universal. Different components can therefore be installed using the
individual terminals.