17
SKOPE BackBar X
Electronic Controller
Service Manual
Parameter
History
To see if the parameters have changed from the factory settings, check the
H5 parameter. If it is a positive value the parameters are still at factory
settings. If H5 is a negative value, the parameters have been changed and
are not at factory settings.
Continued over page
6. Press the
Set (mute)
button to display the value associated with the
parameter code.
7. Use the
ES (up)
and
Light (down)
buttons to increase or decrease the value
of the parameter.
8. Press the
Set (mute)
button to temporarily save the new value. The display
shows the parameter code.
IMPORTANT
If no buttons are pressed for 60 seconds or the power is
disconnected before the temporarily saved values are
permanently saved, the temporarily saved values will be
cancelled and the previous setting will be restored.
9. If necessary, repeat steps 5 - 7 to change other parameters as required.
10. Press and hold the
Set (mute)
button for 3 seconds to permanently save the
parameters and exit the parameter menu.
Category
Initial
Icon
Probe parameters
/
-
Control parameters
r
-
Compressor parameters
c
Defrost parameters
d
Alarm parameters
A
Fan parameters
F