19
SKOPE TME ActiveCore
Electronic Controller
Service Manual
Parameter list - Program 105 - ActiveCore Series Solid Door S4 EVO (continued over page)
Revision:
2.0
Application
ActiveCore Top & Bottom Mount (Solid Door)
Controller Type
SKOPE S4 EVO
Controller Model & Revision
PZSKC0H002K (Rev 1.414)
SKOPE Part Number
ELZ11478-105
Setting
Unit
SET0
Min
Max
Probe Parameters
PS
22
F
0
200
Password (Read Only)
/2
4
C
1
15
Measurement stability (Applies to all probes)
/4
1
C
1
5
Select probe displayed
/5
0
C
0
1
Select °C/°F ( 0=°C ; 1=°F )
/6
0
C
0
1
Disable decimal point
/8
0.0
°C
C
-99.00
99.0
Display Offset (Only if /E > 0)
/9
0.0
°C
C
-40.0
/A
Minimum Display value (Only if /E > 0)
/E
1
C
0
50
Display Dampening Coefficient
/C1
0.0
°C
C
-50.0
50.0
Probe 1 Calibration Offset
/C2
0.0
°C
C
-50.0
50.0
Probe 2 Calibration Offset
/C3
0.0
°C
C
-50.0
50.0
Probe 3 Calibration Offset
Regulation Parameters
St
2.0
°C
F
r1
r2
Set point
rd
2.0
°C
C
0.0
19.0
DAY differential
r1
1.0
°C
C
-50.0
r2
Minimum set point value
r2
15.0
°C
C
r1
150
Maximum set point value
r3
1
C
0
1
Enable Auto Day/Night Mode Switching
r4
1.0
°C
C
-50.0
50.0
Night Mode set point delta (added to St)
r5
2.0
°C
C
0.0
19.0
Night differential
r6
1
hrs
F
0
90
Night Mode Start Delay (time period with no door openings)
r7
90
hrs
F
1
90
Night Mode Timeout (time period in night mode)
r10
0
hrs
C
0
24
Light Delay On Time after entering DAY mode
Cold Climate Protection Parameters
CCt
2.0
°C
C
0.1
20.0
Cold Climate Protection Temperature Delta
CCd
30
mins
C
0
199
Cold Climate Protection Delay
Pull Down Mode Parameters
Pt
127
°C
C
0
127
Pull-down Mode - Activation Temperature
Pd
250
hrs
C
0
250
Pull-down Mode - Maximum Duration
Compressor Parameters
c0
1
mins
C
0
200
Comp. and Fan start delay at power-up.
c1
0
mins
C
0
100
Minimum time between consecutive compressor starts
c2
5
mins
C
0
100
Minimum compressor off time
c3
5
mins
C
0
100
Minimum compressor on time
c4
7
mins
C
0
100
Compressor on time with duty setting
c5
1
C
0
1
Enable mains voltage protection (0 = disabled, 1 = enabled)
Defrost Parameters
d0
0
C
0
1
Type of defrost ( 0 = Electric, 1 = Hot Gas)
dI
2
hrs
C
0
199
Defrost interval time (Time between defrosts)
d2
1
C
0
1
Run defrost interval timer only when compressor running
dt
4.5
°C
C
-50.0
127
Defrost Termination temperature
dP
90
mins
C
1
199
Maximum defrost duration
d4
1
C
0
1
Defrost request at power-on: (0 = no, 1 = yes)
d5
0
mins
C
0
199
Defrost delay on power-up (when d4=1)
d6
1
C
0
1
Display during defrost (0 = "dEF", 1 = Temperature at start of defrost)
dd
0
mins
C
0
15
Dripping time (compressor and fans stopped after defrost)
d8
0
mins
C
0
199
Bypass high temperature alarm after defrost or door opening
d9
0
C
0
1
Defrost priority over compressor protectors
d/1
-
°C
F
-
-
Probe reading on 2nd Input (read only)
Parameter
105
CPS1017-105-SET0
Last revised on
17-Feb-2017
Full List
SET0
Access
Level
Range
Description
Electronic Controller Parameter Sheet