74
Replacement Procedures
Service Manual
SKOPE TME ActiveCore
To reset the high pressure switch
1. Isolate the chiller from the power supply and remove the refrigeration unit
(see page 66).
2. Determine and eliminate what caused the high pressure switch to activate.
3. Remove the refrigeration unit cover.
4. Reset the high pressure switch by pressing the red button on the side of the
refrigeration unit.
5. Reassemble and test for correct operation.