16
Electronic Controller
Service Manual
SKOPE TME ActiveCore
Parameter list - Program 081 - S4 ActiveCore Series
081 - SET0 - ActiveCore Top/Bottom Mount
Revision: 1.1
This sheet is only for use in SKOPE product(s)
ActiveCore Top & Bottom Mount
Controller Type
SKOPE S4
Controller Model & Revision
PZSKC0H001K (Rev 1.211)
SKOPE Part Number
ELZ11042P-081
Setting
Unit
Access
Description of Parameter
Level
Min
Max
Probe Parameters
PS
22
-
F
0
200
Password
/2
4
-
C
1
15
Probe measurement stability
/4
1
-
C
1
3
Select probe displayed
/5
0
-
C
0
1
Select °C/°F (0 = °C, 1 = °F)
/6
0
-
C
0
1
Disable decimal point
/C1
0.0
°C/°F
C
-12.7°C
12.7°C
Probe 1 off set
/C2
0.0
°C/°F
C
-12.7°C
12.7°C
Probe 2 off set
Control Parameters
St
2.0
°C/°F
F
r1
r2
Set point
rd
2.0
°C/°F
C
0.0°C
19°C
DAY differential
r1
1.0
°C/°F
C
-50.0°C
r2
Minimum set point value
r2
15.0
°C/°F
C
r1
150°C
Maximum set point value
r4
1.0
°C/°F
C
1°C
50°C
Night Mode set point delta
r5
2.0
°C/°F
C
0°C
19.0°C
Night differential
r6
3
hrs
F
0
90
Automatic Day to Night Mode: Time Period with Door Closed
r7
9
hrs
F
1
90
Automatic Night to Day Mode: Time Period in Night mode
r8
10
sec
C
0
90
Time allowed for door closure after entering Night mode via keypad
CCt
2.0
°C/°F
H
0.1°C
20.0°C
CCP Mode: Temperature Delta
CCd
30
min
H
0
199
CCP Mode: delay
Compressor Parameters
c0
1
min
C
0
200
Compressor start delay on power-up
c1
0
min
C
0
100
Minimum time between consecutive compressor starts
c2
5
min
C
0
100
Minimum compressor off time
c3
5
min
C
0
100
Minimum compressor on time
c4
7
min
C
0
100
Compressor on time with duty setting
Defrost Parameters
d0
1
-
C
0
2
Type of defrost
dI
2
hrs
C
0
199
Compressor Runtime between Defrosts
dt
4.5
°C/°F
C
-50.0°C
127°C
Defrost Termination Temperature
dP
90
min
C
1
199
Maximum defrost duration
d4
1
-
C
0
1
Defrost when switching the instrument on (0:no 1:yes)
d5
0
min
C
0
199
Defrost delay on power-up (when d4=1)
d6
1
-
C
0
1
Freeze temperature display during defrost
dd
0
min
C
0
15
Dripping time
d8
0
hrs
C
0
15
Bypass high and low temperature alarms (AH,AL) after defrost
d9
0
-
C
0
1
Defrost priority over compressor protectors
d/
-
°C/°F
C
-
-
Defrost probe reading
d10
-10.0
°C/°F
C
-50.0°C
127°C
Start defrost condition: evaporator temperature threshold
d11
127
°C/°F
H
-50.0°C
127°C
Enabling defrost condition: Control probe threshold
d12
200
min
C
A10
200
No Downward Tendency Defrost - Start Delay
d20
20
min
H
0
200
Sample time of Tendency evaluation (minutes)
d21
1
-
H
1
5
Number of allowed defrost before RSF alarm
d22
0.1
°C/°F
H
1.0°C
5.0°C
Temperature gap of Tendency evaluation (°C/°F)
Alarm Parameters
A0
2.0
°C/°F
C
-20°C
20°C
Temperature Alarm Differential
AL
4.0
°C/°F
C
-50°C
150°C
Low Temperature Alarm Setpoint. (Absolute if A0≤0, relative A0>0)
AH
8.0
°C/°F
C
-50°C
150°C
High Temperature Alarm Setpoint. (Absolute if A0≤0, relative A0>0)
Ad
180
min
C
0
199
Temperature Alarm Delay
A10
2
min
C
0
10
Open Door Alarm Delay
Fan Parameters
F0
3
sec
C
1
100
Start delay when FAN ON is required by the Regulation
Fd0
100
min
C
1
100
Fan DAY Duty Cycle : ON time
FdF
1
min
C
1
100
Fan DAY Duty Cycle : OFF time
Fn0
2
min
C
1
100
Fan NIGHT Duty Cycle : ON time
FnF
2
min
C
1
100
Fan NIGHT Duty Cycle : OFF time
Configuration Parameters
H0
1
-
C
0
207
Supervisor Serial address
H4
0
-
C
0
1
Disable buzzer
H5
81
-
C
0
199
ID code (read-only)
Warning:
1. Only make program modifications with reference to relevant Operating Manual.
2. This parameter sheet is exclusively for SKOPE refrigeration systems with its dedicated Carel controller.
3. Any alteration from this program may adversely affect the SKOPE Refrigeration System operation.
4. Specification may change without notice. Please check with Skope Customer Service for latest version.
15 April 2016
Electronic Controller Parameter Sheet
Parameter
Range
Last Revised on
081
Full List
SET0
CPS1016-081-SET0