Installation options
Installation Instructions HELIODENT
PLUS
båÖäáëÜ
empty
Installation option 6.1
Installation option 6.1
Release outside of the X-ray room with remote control, door contact sa
-
fety circuit
● Door contact
– Door contact S7 wired to the remote control housing
● Release
– Manual release S3
or
– Remote control release key S9
empty
Installation option 7
Installation option 7
Release outside of the X-ray room with Remote Timer, door contact sa
-
fety circuit
● Door contact
– Door contact S7
● Release
– Release key on the control membrane S4
empty
Installation option 8
Installation option 8
Release outside of the X-ray room with Remote Timer, door contact sa
-
fety circuit
● Door contact
– Door contact S7 wired to Remote Timer
● Release
– Manual release S3
6.1
L9
S7
S3
S9
NOTICE
Installation requirement
Use of the remote control is permissible only if the yellow X-Ray LED is
visible to the operating personnel during radiation release.
7
L6
S7
S4
8
L6
S7
S3