background image

EA-K-30 – Technical Data

Operating Manual

Chain actuator – EA-K-30/xxx-T(-DA)

Chain actuator

 – EA230-K-30/xxx(-S)

BA_EA(230)-K-30-XXX_EN_12

www.simon-protec.com

Date: 13.02.2019

[email protected]

Issue:  1.2 / 01.2019

Page 24

7. EA-K-30 – Technical Data

Table 1: Electrical properties

Actuator type/version

EA-K-30

Rated voltage

Permissible rated voltage range

Ripple of the rated voltage Vpp

Undervoltage detection

Nominal current

1

1.

Maximum current consumption at nominal load

Maximum starting current in 
“OPEN” and “CLOSED” 
direction

Maximum cut-off current in 
“OPEN” and “CLOSED” 
direction, after start-up

2

2.

Can be configured via SIMON LINK.

soft - close  current

3

3.

Soft - close range: last 75 mm before reaching the “CLOSED” end 
position, soft - close current can be configured via SIMON LINK – current 
range: 0.3 A – 1,0 A; when the speed reduction function is activated 
0.3 A – 0.5 A.

Current consumption after cut-
off (closed current)

Cut-off via

Maximum permissible number 
of actuator units connected in 
parallel in tandem operation

4

4.

With a common cut-off function (tandem function).

Cable length between two 
actuators in tandem operation

Tandem run-on time

5

5.

The tandem run-on time indicates how long the actuator connected in 
parallel continues to run after cutting off the triggering actuator.

The run-on time is 3 s in each case 50 mm before reaching the end 
position and 0 s in the range between (see Figure 10: “Configurable 
ranges” on page 8).

Pulse time

6

6.

The pulse time indicates how long the internal or external overload cut-
off provides the cut-off signal at the output.

Protection class

 

Table 2: Dry contact (NO1, NO2)

Actuator type/version

EA-K-30

Rated voltage

Contact load relay

The normally open contact (NO) is only activated in the 
“CLOSED” end position when the actuator is cut off. This 
means that the message is stroke-dependent and can be 
evaluated as a “CLOSED message”. Activation of the 
actuator at the “OPEN” end position can also be configured 
via SIMON LINK, as well as other settings.

Table 3: Connection and operation

Actuator type/version

EA-K-30

Silicone connection cable with 
connector

Supply cable length

1

1.

Optional lengths possible.

Pause time at a change in the 
driving direction

2

2.

It is necessary that the supply voltage ensures a pause time (zero volt 
range) of at least 500 ms for a change in the driving direction (pole 
reversal) (see Figure 29: “Zero volt range at a change in the driving 
direction” on page 25).

Switch-on duration

S2 ED 30% (short-time duty

Stability of opening and closing 
cycles

Sound level

3

3.

Measured at a distance of one metre under normal conditions. 

Re-triggering in accordance 
with prEN 12101-9

Re-triggering after a stop

Maintenance

24 V DC

24 V DC -15%; +15%

max. 500 mV

yes

1.0 A

1.1 A

1.1 A

0.3 A

40 mA

Integrated electronic overload 

cut-off

2 in DUO operation

4 in parallel operation

(see chapter 6.2 “EA-K-30 

Electrical connection” on 

page 19)

max. 10 m

3 s

300 ms

III 

max. 28 V DC

1.0 A

ATTENTION

The maximum load capacity of the contact must not be 
exceeded (see Table 2: “Dry contact (NO1, NO2)”).

INFORMATION

The output of the dry contact occurs only on the gear side 
of the actuator (see Figure 1: “EA-K-30/xxx-T(-DA) chain 
actuator” on page 5)!

5 x 0.75 mm²

 3 m

at least 500 ms

3 of 10 minutes)

11

 

000

 55 dB (A)

permitted

permitted

See chapter 11.1 “Care and 

Maintenance” on page 28.

Summary of Contents for EA-K-30 Series

Page 1: ...lementary sheet Safety Instructions and Warranty Conditions Operating Manual Valid for the following article numbers EA K 30 xxx T DA M2 5315 DA 400 mm stroke M2 5316 DA 600 mm stroke M2 5317 DA 800 m...

Page 2: ...erforming a teach in run 9 5 7 LED displays 10 6 Mounting 11 6 1 Mechanical connection 11 6 1 1 Mounting brackets 12 6 1 2 Top bracket K K50 OK 13 6 1 3 Inward opening bracket K K30 AKI 14 6 1 4 Top b...

Page 3: ...K 30 xxx 22 6 4 1 Parallel connection EA230 K 30 xxx 23 6 4 2 Synchronous connection EA230 K 30 xxx S 23 7 EA K 30 Technical Data 24 8 EA230 K 30 Technical Data 26 9 Commissioning 27 9 1 EA230 K 30 27...

Page 4: ...installed in walls or in roofs and are used for the ventilation of rooms or for the removal of fire smoke See chapter 2 1 Risk assessment on page 5 1 3 EA K 30 Product description The EA K 30 xxx T DA...

Page 5: ...dance sheet KB 01 Power operated windows issued by the VFF window door and facade manufacturers www eurowindoor eu news and proceeding position papers and publications ATTENTION A restrictor stay with...

Page 6: ...X_EN_12 www simon protec com Date 13 02 2019 info simon protec com Issue 1 2 01 2019 Page 6 Figure 3 Top bracket K K50 OK Figure 4 Top bracket K K OK SK Figure 5 Inward opening bracket K K30 AKI Figur...

Page 7: ...rection The soft close current can be adjusted The speed reduction before the CLOSED end position for the soft close range can be set see Figure 10 Configurable ranges on page 8 The switching behaviou...

Page 8: ...tely closed and moved into the gaskets After the window is closed each time or the cut off current has been exceeded the chain is extended slightly again to protect the gaskets and the window 5 2 End...

Page 9: ...nect the chain end piece to the top bracket again Let the actuator perform a teach in run see chapter 5 6 Performing a teach in run on page 9 5 5 Teach in run The actuators detect and store the distan...

Page 10: ...actuators does not match Check and correct the connection of the actuators 7 Addressing error Synchro The assignment of the internal addresses of interconnected actuators has failed Perform a RESET pr...

Page 11: ...al memory of the actuator is running Continuously lighting RESET procedure is running Continuously lighting for 3 sec Teach in procedure of the teach in run has been completed correctly Flashing RESET...

Page 12: ...tion of the chain is in the centre of the window centre line markings are provided on the K K 50 OK for this purpose see Figure 14 on page 13 In parallel duo operation the actuators should be position...

Page 13: ...bracket must always be aligned in such a way that the SIMON logo on the bracket is on the same side of the chain as the SIMON logo on the chain exit INFORMATION Centre line marking see Figure 14 for a...

Page 14: ...r side with the retaining ring 3 Figure 18 ATTENTION In the case of a compression force application e g top hung window the mounting bracket must always be aligned so that the SIMON logo of the bracke...

Page 15: ...hung window mounting on a blind frame Figure 21 Outward opening top hung window ATTENTION The top bracket must always be aligned in such a way that the SIMON logo on the bracket is on the same side o...

Page 16: ...1 7 Inward opening top bottom hung window actuator mounted on the window sash Figure 22 Inward opening bottom hung window at the window sash 6 1 8 Inward opening bottom hung window actuator K K30 FLE...

Page 17: ...EA 230 K 30 XXX_EN_12 www simon protec com Date 13 02 2019 Issue 1 2 01 2019 info simon protec com 6 1 9 Rotary window Figure 24 Mounted on a blind frame Figure 25 Mounted on the window sash ATTENTION...

Page 18: ...ce of the actuator N S the stroke of the actuator mm H the height of the window sash mm W the weight of the window sash kg Required actuator force for the specified stroke F W 2 x S H x 10 W x S x 5 H...

Page 19: ...ossible to supply power to the second actuator directly through the first actuator DA variant in tandem duo operation The supply cable can therefore be changed into a connection cable Cut the second s...

Page 20: ...nnection dry contact Connect the cables according to the connection plan 6 2 7 Single connection F contact Connect the cables according to the connection plan INFORMATION The output of the dry contact...

Page 21: ...actuator DA brown NO2 O black yellow red blue T NO1 S 2 actuator brown NO2 O red O S T blue brown red connected internally connection cable black yellow black yellow 24V DC OPEN S O CLOSE pole change...

Page 22: ...DA V4 regulations and the workplace regulation ASR A 1 6 All the relevant national safety regulations and directives apply when installing commissioning and putting the actuator into operation outside...

Page 23: ...LZ LA LZ LA 0 brown blue black max 8 actuators in parallel behind a switching element brown black blue factory provided 6 4 2 Synchronous connection EA230 K 30 xxx S Connect the cables according to th...

Page 24: ...t the output Protection class Table 2 Dry contact NO1 NO2 Actuator type version EA K 30 Rated voltage Contact load relay The normally open contact NO is only activated in the CLOSED end position when...

Page 25: ...7 7 Plus chain exit 7 mm x D EA K 30 400 T DA EA K 30 600 T DA EA K 30 800 T DA EA K 30 1000 T DA EA K 30 1200 T DA Weight8 8 Information without supply cable and brackets EA K 30 400 T DA EA K 30 600...

Page 26: ...Installation and ambient conditions Actuator type version EA230 K 30 Nominal operating temperature Permissible ambient temperature range Protection rating Area of application Table 11 Approvals and ce...

Page 27: ...S EA230 K 30 800 S EA230 K 30 1000 S 0 90 kg 1 40 kg 1 80 kg 2 20 kg 1 Only under optimum conditions up to a 600 mm stroke see chapter 6 1 11 Permissible pushing force on the chain on page 18 2 The f...

Page 28: ...Deutschland GmbH Medienstra e 8 94036 Passau Tel 49 0 851 379368 0 Fax 49 0 851 379368 70 SIMON PROtec Deutschland GmbH Ammerseestra e 75 D 82061 Neuried Tel 49 0 89 79170 11 Fax 49 0 89 79179 72 E Ma...

Reviews: