background image

EA230-K-30 – Functions

Operating Manual

Chain actuator – EA-K-30/xxx-T(-DA)

Chain actuator

 – EA230-K-30/xxx(-S)

Page 9

BA_EA(230)-K-30-XXX_EN_12

www.simon-protec.com

Date: 13.02.2019

Issue:  1.2 / 01.2019

[email protected]

5.4 RESET

If necessary, release the connection between the chain 
end piece and the top bracket.

Drive the actuator in the OPEN direction and extend the 
chain by approx. 10 cm.

Disconnect the actuator from the power supply.

Check the communication cables in the case of actuators 
connected in parallel (red / white).

Set both of the DIP switches 1 and 2 to OFF.

Wait for five seconds.

Drive the actuator in the OPEN direction.

 

The RESET procedure is performed, the orange LED 

lights up continuously during this procedure. The 
actuator immediately moves in the CLOSED direction 
up to the end position, then approx. 5 cm back in 
OPEN direction.

 

The orange LED flashes continuously after performing 

the RESET process correctly.

Disconnect the actuator from the power supply again.

Set the DIP switches 1 and 2 to the desired setting.

Wait for five seconds.

Connect the chain end piece to the top bracket again.

Let the actuator perform a teach-in run 

(see chapter 5.6 “Performing a teach-in run” on page 9).

5.5 Teach-in run

The actuators detect and store the distance between sash 
and frame fully automatically during operation (when the 
window is fully closed). The dimensional difference between 
wing and frame is called overhang.

This teach-in takes place when the actuator fully closes the 
window for the first time after a RESET.

5.6 Performing a teach-in run

Open the actuator slightly and then drive it in the 
CLOSED direction and let it cut off in the end position.

 

If the teach-in process has worked correctly, the 

actuator signals this by the flashing of the orange LED 
(next to the DIP switches) for approx. 3 seconds.

If the orange LED does not flash as described, a RESET 
must initially be performed (see chapter 5.4 “RESET“).

ATTENTION

The chain end piece must not be connected to the bracket 
when performing the RESET process.

ATTENTION

The communication cables of the actuators must be 
connected to each other during the RESET process in 
synchronous mode (red with red and white with white).

ATTENTION

After RESET, e.g. after a stroke setting via the DIP 
switches or after installation, you must perform a teach-in 
run.

Summary of Contents for EA-K-30 Series

Page 1: ...lementary sheet Safety Instructions and Warranty Conditions Operating Manual Valid for the following article numbers EA K 30 xxx T DA M2 5315 DA 400 mm stroke M2 5316 DA 600 mm stroke M2 5317 DA 800 m...

Page 2: ...erforming a teach in run 9 5 7 LED displays 10 6 Mounting 11 6 1 Mechanical connection 11 6 1 1 Mounting brackets 12 6 1 2 Top bracket K K50 OK 13 6 1 3 Inward opening bracket K K30 AKI 14 6 1 4 Top b...

Page 3: ...K 30 xxx 22 6 4 1 Parallel connection EA230 K 30 xxx 23 6 4 2 Synchronous connection EA230 K 30 xxx S 23 7 EA K 30 Technical Data 24 8 EA230 K 30 Technical Data 26 9 Commissioning 27 9 1 EA230 K 30 27...

Page 4: ...installed in walls or in roofs and are used for the ventilation of rooms or for the removal of fire smoke See chapter 2 1 Risk assessment on page 5 1 3 EA K 30 Product description The EA K 30 xxx T DA...

Page 5: ...dance sheet KB 01 Power operated windows issued by the VFF window door and facade manufacturers www eurowindoor eu news and proceeding position papers and publications ATTENTION A restrictor stay with...

Page 6: ...X_EN_12 www simon protec com Date 13 02 2019 info simon protec com Issue 1 2 01 2019 Page 6 Figure 3 Top bracket K K50 OK Figure 4 Top bracket K K OK SK Figure 5 Inward opening bracket K K30 AKI Figur...

Page 7: ...rection The soft close current can be adjusted The speed reduction before the CLOSED end position for the soft close range can be set see Figure 10 Configurable ranges on page 8 The switching behaviou...

Page 8: ...tely closed and moved into the gaskets After the window is closed each time or the cut off current has been exceeded the chain is extended slightly again to protect the gaskets and the window 5 2 End...

Page 9: ...nect the chain end piece to the top bracket again Let the actuator perform a teach in run see chapter 5 6 Performing a teach in run on page 9 5 5 Teach in run The actuators detect and store the distan...

Page 10: ...actuators does not match Check and correct the connection of the actuators 7 Addressing error Synchro The assignment of the internal addresses of interconnected actuators has failed Perform a RESET pr...

Page 11: ...al memory of the actuator is running Continuously lighting RESET procedure is running Continuously lighting for 3 sec Teach in procedure of the teach in run has been completed correctly Flashing RESET...

Page 12: ...tion of the chain is in the centre of the window centre line markings are provided on the K K 50 OK for this purpose see Figure 14 on page 13 In parallel duo operation the actuators should be position...

Page 13: ...bracket must always be aligned in such a way that the SIMON logo on the bracket is on the same side of the chain as the SIMON logo on the chain exit INFORMATION Centre line marking see Figure 14 for a...

Page 14: ...r side with the retaining ring 3 Figure 18 ATTENTION In the case of a compression force application e g top hung window the mounting bracket must always be aligned so that the SIMON logo of the bracke...

Page 15: ...hung window mounting on a blind frame Figure 21 Outward opening top hung window ATTENTION The top bracket must always be aligned in such a way that the SIMON logo on the bracket is on the same side o...

Page 16: ...1 7 Inward opening top bottom hung window actuator mounted on the window sash Figure 22 Inward opening bottom hung window at the window sash 6 1 8 Inward opening bottom hung window actuator K K30 FLE...

Page 17: ...EA 230 K 30 XXX_EN_12 www simon protec com Date 13 02 2019 Issue 1 2 01 2019 info simon protec com 6 1 9 Rotary window Figure 24 Mounted on a blind frame Figure 25 Mounted on the window sash ATTENTION...

Page 18: ...ce of the actuator N S the stroke of the actuator mm H the height of the window sash mm W the weight of the window sash kg Required actuator force for the specified stroke F W 2 x S H x 10 W x S x 5 H...

Page 19: ...ossible to supply power to the second actuator directly through the first actuator DA variant in tandem duo operation The supply cable can therefore be changed into a connection cable Cut the second s...

Page 20: ...nnection dry contact Connect the cables according to the connection plan 6 2 7 Single connection F contact Connect the cables according to the connection plan INFORMATION The output of the dry contact...

Page 21: ...actuator DA brown NO2 O black yellow red blue T NO1 S 2 actuator brown NO2 O red O S T blue brown red connected internally connection cable black yellow black yellow 24V DC OPEN S O CLOSE pole change...

Page 22: ...DA V4 regulations and the workplace regulation ASR A 1 6 All the relevant national safety regulations and directives apply when installing commissioning and putting the actuator into operation outside...

Page 23: ...LZ LA LZ LA 0 brown blue black max 8 actuators in parallel behind a switching element brown black blue factory provided 6 4 2 Synchronous connection EA230 K 30 xxx S Connect the cables according to th...

Page 24: ...t the output Protection class Table 2 Dry contact NO1 NO2 Actuator type version EA K 30 Rated voltage Contact load relay The normally open contact NO is only activated in the CLOSED end position when...

Page 25: ...7 7 Plus chain exit 7 mm x D EA K 30 400 T DA EA K 30 600 T DA EA K 30 800 T DA EA K 30 1000 T DA EA K 30 1200 T DA Weight8 8 Information without supply cable and brackets EA K 30 400 T DA EA K 30 600...

Page 26: ...Installation and ambient conditions Actuator type version EA230 K 30 Nominal operating temperature Permissible ambient temperature range Protection rating Area of application Table 11 Approvals and ce...

Page 27: ...S EA230 K 30 800 S EA230 K 30 1000 S 0 90 kg 1 40 kg 1 80 kg 2 20 kg 1 Only under optimum conditions up to a 600 mm stroke see chapter 6 1 11 Permissible pushing force on the chain on page 18 2 The f...

Page 28: ...Deutschland GmbH Medienstra e 8 94036 Passau Tel 49 0 851 379368 0 Fax 49 0 851 379368 70 SIMON PROtec Deutschland GmbH Ammerseestra e 75 D 82061 Neuried Tel 49 0 89 79170 11 Fax 49 0 89 79179 72 E Ma...

Reviews: