User manual - METER SRP-946
Register
Write
Range
Register description
57h
Yes
0 ÷ 999
“t on”
parameter in
“rEL3”
menu, expressed in tenth of seconds or
tenth of minutes depend on
“unit”
parameter - register no. 59h)
58h
Yes
0 ÷ 999
“toFF”
parameter in
“rEL3”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter - register no. 59h)
59h
Yes
0 ÷ 1
“unit”
parameter in
“rEL3”
menu:
0
- seconds;
1
- minutes
5Ah
Yes
0 ÷ 2
“AL”
parameter in
“rEL3”
menu:
0
- no changes;
1
- on;
2
- off
5Bh
Yes
see descr.
“
SEt2
” parameter in “
rEL3
” menu, no decimal point included –
higher word
5Ch
Yes
see descr.
“
SEt2
” parameter in “
rEL3
” menu, no decimal point included –
lower word
5Dh
Yes
see descr.
“
SEtP
” parameter in “
rEL4
” menu, no decimal point included –
higher word
5Eh
Yes
see descr.
“
SEtP
” parameter in “
rEL4
” menu, no decimal point included – lower
word
5Fh
Yes
see descr.
“
HySt
” parameter in “
rEL4
” menu, no decimal point included –
higher word
60h
Yes
see descr.
“
HySt
” parameter in “
rEL4
” menu, no decimal point included –
lower word
61h
Yes
0 ÷ 5
“
modE
” parameter in “
rEL4
” menu:
0
- “
noAC
” mode;
1
- “
on
” mode;
2
- “
oFF
” mode;
3
- “
in
” mode;
4
- “
out
” mode;
5
- “
modb
” mode
62h
Yes
0 ÷ 999
“t on”
parameter in
“rEL4”
menu, expressed in tenth of seconds or
tenth of minutes depend on
“unit”
parameter - register no. 64h)
63h
Yes
0 ÷ 999
“toFF”
parameter in
“rEL4”
menu, expressed in tenth of seconds
or tenth of minutes depend on
“unit”
parameter - register no. 64h)
64h
Yes
0 ÷ 1
“unit”
parameter in
“rEL4”
menu:
0
- seconds;
1
- minutes
65h
Yes
0 ÷ 2
“AL”
parameter in
“rEL4”
menu:
0
- no changes;
1
- on;
2
- off
66h
Yes
see descr.
“
SEt2
” parameter in “
rEL4
” menu, no decimal point included –
higher word
67h
Yes
see descr.
“
SEt2
” parameter in “
rEL4
” menu, no decimal point included –
lower word
68h
Yes
0 ÷ 1
“
modE
” parameter in “
HOLd
” menu (type of detected changes):
0
- peaks;
1
- drops
69h
Yes
see descr.
“
PEA
” parameter in “
HOLd
” menu (minimum detectable change, no
decimal point included) – higher word
6Ah
Yes
see descr.
“
PEA
” parameter in “
HOLd
” menu (minimum detectable change, no
decimal point included) – lower word
6Bh
Yes
0 ÷ 199
“
timE
” parameter in “
HOLd
” menu,
maximum peaks' (or drops')
display time expressed in seconds
54