User manual - METER SRP-946
Register
Write
Range
Register description
6Ch
Yes
0 ÷ 1
“
HdiS
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
6Dh
Yes
0 ÷ 1
“
H r1
” parameter in “
HOLd
” menu
:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
6Eh
Yes
0 ÷ 1
“
H r2
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
6Fh
Yes
0 ÷ 1
“
H r3
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
70h
Yes
0 ÷ 1
“
H r4
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
71h
Yes
0 ÷ 1
“
HOUt
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
77h
5
Yes
see descr.
The value of „
X
” coordinate of point
no. 1
of the user defined
characteristic, expressed in 0.1% – higher word
78h
5
Yes
see descr.
The value of „
X
” coordinate of point
no. 1
of the user defined
characteristic, expressed in 0.1% – lower word
79h
5
Yes
see descr.
The value of „
Y
” coordinate of point
no. 1
of the user defined
characteristic, no decimal point included – higher word
7Ah
5
Yes
see descr.
The value of „
Y
” coordinate of point
no. 1
of the user defined
characteristic, no decimal point included – lower word
7Bh
5
÷ C2h
5
Further pairs of „
X
” - „
Y
” coordinates of points
no. 2
÷
19
of the
user defined characteristic
C3h
5
Yes
see descr.
The value of „
X
” coordinate of point
no. 20
of the user defined
characteristic, expressed in 0.1% – higher word
C4h
5
Yes
see descr.
The value of „
X
” coordinate of point
no. 20
of the user defined
characteristic, expressed in 0.1% – lower word
C5h
5
Yes
see descr.
The value of „
Y
” coordinate of point
no. 20
of the user defined
characteristic, no decimal point included – higher word
C6h
5
Yes
see descr.
The value of „
Y
” coordinate of point
no. 20
of the user defined
characteristic, no decimal point included – lower word
D0h
1
Yes
0 ÷ 3
“
Omod
” parameter in “
OUtP
” menu (active current output mode)
0
-
current output disabled
;
1
-
current output enabled
with
4
÷
20mA
mode;
2
-
current output enabled with
0÷20mA
mode
;
3
-
current output controlled via RS-485 interface
Yes
0 ÷ 2
“
Omod
” parameter in “
OUtP
” menu (passive current output mode)
0
-
current output disabled
;
1
-
current output enabled
with
4
÷
20mA
mode;
2
-
current output controlled via RS-485 interface
Yes
0 ÷ 5
“
Omod
” parameter in “
OUtP
” menu (active voltege output mode)
0
- voltage
output disabled
;
1
- voltage
output enabled
with
0
÷5V
mode;
2
- voltage
output enabled with
1÷5V
mode
;
3
- voltage
output enabled with
0÷10V
mode
;
4
- voltage
output enabled with
2÷10V
mode
;
5
- voltage
output controlled via RS-485 interface
55