8
directions requested by the Norms and a
few practical considerations:
– With direct external suction, when the
duct is greater than 1 m in length, insu-
lation is recommended in order to avoid,
in particularly cold periods, the formation
of dew on the outside of the tubing.
– With discharge duct positioned on the
outside of the building, or in cold environ-
ments, insulation is necessary to avoid
starting failures of the burner. In such
cases, a system for the collection of con-
densation must organised.
– If a segment of the flue passes through
a flammable wall, this segment must be
insulated with a glass wool pipe insula-
tor 30 mm thick, with a density of 50
kg/m
3
.
The maximum total length obtained by
summing up the lengths of the suction and
discharge tubing is determined by the load
losses of the single fittings attached
(excluding the splitter) and must not be
greater than 9.00 mm H
2
O.
For the load
losses of the fittings refer to
Table 4.
3.8.1
Separate ducts accessories
For the realisation of this type of discharge
is supplied a kit cod. 8093000 (fig. 14).
The sector diaphragm in the kit, must be
used according to the maximum load loss
allowed in both ducts, as indicated in fig.
14/a. The complete range of accessories
necessary for each type of installation are
given in fig. 15.
3.8.2
Roof outlet separate ducts
The roof outlet terminal L. 1240 cannot be
shortened and in the positioning of the tile
the distance from the discharge outlet of
the terminal must not be less than 700
mm (fig. 16). The accessories necessary
for this type of discharge and some of the
other type of systems that it is possible to
use are shown in fig. 16.
By utilising the doubler fitting (7 fig. 17) it is
possible to have a concentric discharge. In
these cases, during assembly, it is neces-
sary to get the washer in silicon used on
the reduction of the terminal (5 fig. 16) to
be substituted with the doubler and place it
in the housing of the doubler.
For this type of discharge the sum of the
maximum development allowed of the
ducts must not be greater than 9.00 mm
H
2
O.
To calculate the load losses of the sin-
gle fittings attached refer to
Table 4.
TABLE 4
Accessories ø 80
Head loss (mm H
2
O)
Inlet
Outlet
Roof outlet
90° elbow MF
0,30
0,40
–
45° elbow MF
0,20
0,30
–
Extension L. 1000 (horizontal)
0,20
0,30
–
Extension L. 1000 (vertical)
0,30
0,20
–
Outlet terminal
–
0,30
–
Intake terminal
0,10
–
–
Doubler fitting
0,50
1,50
–
Roof outlet terminal L.1240
–
–
0,50
Tee condensation outlet
–
0,90
–
Example of allowable installation calculation in that the sum of the head losses of
the single fittings is less than 9.00 mm H
2
O:
Intake
Outlet
7 meter horizontal pipe ø 80 x 0.20
1.40
–
7 meter vertical pipe ø 80 x 0.30
–
2.10
n° 2 90° elbows ø 80 x 0.30
0.60
–
n° 2 90° elbows ø 80 x 0.40
–
0.80
N° 1 terminal ø 80
0.10
0.30
Total head loss
2.10
+
3.20 =
5.3 mm H
2
O
With this total head loss, remove the ø 38 baffle from the intake pipe.
105 120
150
ø80
4
3
1
2
Fig. 14
KEY
1
Fixing screw
2
Sponge washer ø 125/95
3
Air-smokes flow splitting unit
with take-off points
4
Sector diaphragm ø 38
Sections of diaphragm
Total load loss
to removed
mm H
2
O
Pa
4
0÷4
0÷39,2
5
4÷5
39,2÷49,0
6
5÷6
49,0÷58,8
Remove diaphragm
6÷9
58,8÷88,2
Fig. 14/a
SECTOR OF DIAPHRAGM
Summary of Contents for Planet Super 4 F.S.
Page 1: ...Planet Super 4 F S Installation Servicing Instructions GB...
Page 27: ......
Page 29: ...Planet Super 4 F S User Instructions GB...
Page 30: ......
Page 41: ...Planet Super 4 W M...
Page 74: ......
Page 75: ......