33
Load loss accessory Ø 80 mm
Description
Code
Load loss (mm H
2
O)
Edea 25 T
Inlet
Outlet
90° curve MF
8077450
0,20
0,25
45° curve MF
8077451
0,15
0,15
Horizontal extension W. 1000
mm
8077351
0,15
0,15
Vertical extension W. 1000
mm
8077351
0,15
0,15
Wall terminal
8089501
0,10
0,25
Roof outlet terminal (*)
8091204
0,80
0,10
Duct kit C(10)3
6296550
-
1,2
6296543
-
-
Description
Code
Load loss (mm H
2
O)
Edea 35 T
Inlet
Outlet
90° curve MF
8077450
0,30
0,4
45° curve MF
8077451
0,25
0,25
Horizontal extension W. 1000
mm
8077351
0,25
0,25
Vertical extension W. 1000
mm
8077351
0,25
0,25
Wall terminal
8089501
0,15
0,50
Roof outlet terminal (*)
8091204
1,5
0,2
Duct kit C(10)3
6296543
-
2,2
(*) The losses of the roof outlet terminal at inlet include the
manifold code 8091400.
NOTE:
for the boiler to operate correctly it is necessary that a
minimum distance of 0.50 m of the duct is respected with a
90° inlet curve.
6.12.6 Separate ducts (Ø 50 mm)
The
Edea T
boiler is configured for use in Ø 50 mm discharge
flues. To ensure correct boiler operation, parameter PAR31
(long flues) should be set on the basis of the length of the in-
stalled flues, as indicated in the table.
PAR 31
Edea 25 T
Edea 35 T
Ø 50 mm
outlet
Discharge
diaphragm
Ø 50 mm
outlet
Discharge
diaphragm
0
1 x 90° elbow
+ 6 metres
leave it
mounted
1 x 90° elbow
+ 2 metres
remove
0
1 x 90°
elbow + 10
metres
remove
-
-
2
-
-
1 x 90° elbow
+ 6 metres
remove
4
1 x 90°
elbow + 14
metres
remove
1 x 90° elbow
+ 8 metres
remove
6
1 x 90°
elbow + 18
metres
remove
1 x 90°
elbow + 10
metres
remove
8
1 x 90°
elbow + 22
metres
remove
1 x 90°
elbow + 12
metres
remove
10
1 x 90°
elbow + 26
metres
remove
-
-
12
1 x 90°
elbow + 30
metres
remove
-
-
NOTE:
to remove the discharge diaphragm, proceed as illus-
trated in “Fig. 27”.
Example: calculation of the load loss of a
Edea 25 T
boiler.
Accessories Ø 80 mm
Code
Quan-
tity
Load loss (mm H
2
O)
Inlet
Outlet
Total
Extension W. 1000 mm
(horizontal)
8077351
7
7 x 0,15
-
1,05
Extension W. 1000 mm
(horizontal)
8077351
7
-
7 x 0,15
1,05
90° curve
8077450
2
2 x 0,20
-
0,40
90° curve
8077450
2
-
2 x 0,25
0,50
Wall terminal
8089501
2
0,10
0,25
0,35
TOTAL
3,35
(installation permitted since the total of the load loss of the
accessories used is less than 15 mm H
2
O).
120
Ø 80
170
170
Ø 80
320
400
125
125
Fig. 29
6.12.7 Separate ducts (Ø 80mm) with duct kit C(10)3
The
Edea T
boiler is configured for use with type C(10)3 dis-
charge ducts. To ensure correct boiler operation, certain pa-
rameters should be modified in relation to the power and type
of fuel used to power the device.
Set the parameters as specified in the table.
Type
No. Description
Setting for
Edea T
25
35
METH-
ANE
LPG
METH-
ANE
LPG
PAR
09 Ignition revolu-
tions
-
160
-
-
PAR
21 CH/DHW mini-
mum power
6
12
10
8
Duct kit C(10)3 code
6296543 6296550 6296543 6296543
NOTE:
To modify the parameters in the table, proceed as spec-
ified in the paragraph "Parameter setting and display". If the
kit is installed on the Edea 25 T running on LPG, replace the
discharge diaphragm with the one present in the kit; to re-
move the discharge diaphragm, proceed as shown in "Fig. 27".