43
7.6
Checks
7.6.1 Chimney sweep function
The chimney sweeper function is used by the qualified mainte-
nance technician to check the mains gas pressure, detect the
combustion parameters and to measure the combustion effi-
ciency. A combustion analysis should not be conducted until a
satisfactory inlet working pressure test has been completed.
This function lasts 15 minutes and is activated by proceeding
as follows:
– if the panel (2) has not already been removed, remove the
two screws (1), pull the front panel (2) forwards and release
it from the top by lifting it
1
2
Fig. 48
– remove the screws (3) securing the control panel (4)
– move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
3
a
b
5
4
Fig. 49
– isolate the gas cock
– loosen the screw of the “gas mains pressure point” (6) and
connect a pressure gauge
8
7
6
Fig. 50
– open the gas cock
– power the boiler by setting the main switch to "ON"
ON
Fig. 51
– press the button
y
for at least 1 second until "SUMMER"
mode
l
has been selected
– simultaneously press the
y
and
>
buttons, for ~ 10 s, to
start the procedure, until “Hi” appears steady on the display
and the
l
and
n
symbols flash
– press the button
>
to make the boiler operate at maximum
power "Hi" and check that the mains gas pressure value on
the pressure gauge is correct.
– check that the gas supply pressure is as shown in the table
below
Type of gas
G20
G31
Pressure (mbar)
20
37