L1 Controller Error Messages
007-4701-003
125
Table 5-2
L1 Controller Messages
L1 System Controller Message
Message Meaning and Action Needed
Internal voltage messages:
ATTN: x.xV high fault limit reached @ x.xxV
30-second power-off sequence for the module.
ATTN: x.xV low fault limit reached @ x.xxV
30-second power-off sequence for the module.
ATTN: x.xV high warning limit reached @
x.xxV
A higher than nominal voltage condition is
detected.
ATTN: x.xV low warning limit reached @ x.xxV A lower than nominal voltage condition is
detected.
ATTN: x.xV level stabilized @ x.xV
A monitored voltage level has returned to
within acceptable limits.
Fan messages:
ATTN: FAN # x fault limit reached @ xx RPM
A fan has reached its maximum RPM level. The
ambient temperature may be too high. Check to
see if a fan has failed.
ATTN: FAN # x warning limit reached @ xx
RPM
A fan has increased its RPM level. Check the
ambient temperature. Check to see if the fan
stabilizes.
ATTN: FAN # x stabilized @ xx RPM
An increased fan RPM level has returned to
normal.
Temperature messages: low alt.
ATTN: TEMP # advisory temperature reached
@ xxC xxF
The ambient temperature at the module’s air
inlet has exceeded 30 ºC.
ATTN: TEMP # critical temperature reached
@ xxC xxF
The ambient temperature at the module’s air
inlet has exceeded 35 ºC.
ATTN: TEMP # fault temperature reached
@ xxC xxF
The ambient temperature at the module’s air
inlet has exceeded 40 ºC.
Temperature messages: high alt.
ATTN: TEMP # advisory temperature reached
@ xxC xxF
The ambient temperature at the module’s air
inlet has exceeded 27 ºC.