L1 Controller Error Messages
007-4566-001
207
Temperature messages: low alt.
ATTN: TEMP # advisory temperature reached
@ xxC xxF
The ambient temperature at the module’s air
inlet has exceeded 30 ºC.
ATTN: TEMP # critical temperature reached
@ xxC xxF
The ambient temperature at the module’s air
inlet has exceeded 35 ºC.
ATTN: TEMP # fault temperature reached
@ xxC xxF
The ambient temperature at the module’s air
inlet has exceeded 40 ºC.
Temperature messages: high alt.
ATTN: TEMP # advisory temperature reached
@ xxC xxF
The ambient temperature at the module’s air
inlet has exceeded 27 ºC.
ATTN: TEMP # critical temperature reached
@ xxC xxF
The ambient temperature at the module’s air
inlet has exceeded 31 ºC.
ATTN: TEMP # fault temperature reached @
xxC xxF
The ambient temperature at the module’s air
inlet has exceeded 35 ºC.
Temperature stable message:
ATTN: TEMP # stabilized @ xxC/xxF
The ambient temperature at the module’s air
inlet has returned to an acceptable level.
Power off messages:
Auto power down in xx seconds
The L1 controller has registered a fault and is
shutting down. The message displays every
five seconds until shutdown.
Base module appears to have been powered
down
The L1 controller has registered a fault and has
shut down.
Table 7-2
L1 Controller Messages
(continued)
L1 System Controller Message
Message Meaning and Action Needed
Summary of Contents for Origin 350
Page 1: ...SGI Origin 350 Server System User s Guide 007 4566 001 ...
Page 3: ...007 4566 001 iii Record of Revision Version Description 001 June 2003 Original publication ...
Page 4: ......
Page 16: ......
Page 26: ......
Page 50: ...24 007 4566 001 1 Installation and Operation Figure 1 11 Location of Table mounting Feet ...
Page 90: ......
Page 158: ......
Page 180: ......
Page 228: ......
Page 262: ......
Page 274: ......