Troubleshooting
0 0 7 - 5 5 3 3 - 0 0 1
66
4.2.3
System Faults
4.2.4
Power Supply/Cooling Faults
Symptom
Cause
Action
1.
The System Fault LED
turns amber on front panel.
The ESI processor has
detected an internal fault
(for example, failure of an
internal communications
path)
1.
Check for other amber LED
indications on the power cooling
modules. If there is a PSU error present
there may be a communications problem
with that power cooling module.
Remove and then re-fit the module. If
the problem persists, then replace the
module.
2.
Check for other amber LED
indications on the drive modules. If none
are evident, then there may either be an
ESI processor problem or a backplane
problem.
Symptom
Cause
Action
1.
System Fault LED is
amber on front panel.
2.
An amber LED on one or
more power cooling
modules.
1.
Any power fault
2.
A fan failure
3.
A thermal condition
which could cause PSU
overheating
1.
Ensure that the power On/Off switch
on rear of power cooling module is
turned ON.
2.
Ensure that the AC main connection to
the power cooling module is live.
3
. Disconnect the power cooling module
from the main power, remove the
module from the system, and re-install
the module. If the problem persists,
replace the power cooling module.
4
. Reduce the ambient temperature.
Summary of Contents for InfiniteStorage 6120
Page 1: ...SGI InfiniteStorage 6120 RAID User s Guide 007 5533 001 ...
Page 10: ......
Page 11: ...SECTION 1 Introducing the InfiniteStorage 6120 ...
Page 12: ......
Page 23: ...SECTION 2 InfiniteStorage 6120 Installation ...
Page 24: ......
Page 32: ......
Page 43: ...SECTION 3 InfiniteStorage 6120 Management ...
Page 44: ......
Page 66: ......
Page 68: ......
Page 69: ...SECTION 4 Supporting the InfiniteStorage 6120 ...
Page 70: ......
Page 85: ...SECTION 5 Appendices ...
Page 86: ......
Page 94: ......