Appendix B: The raid5 Command Line Interface
There is no output for raid5 with the chglun parameter. Errors are printed to
stderr.
clearlog
The clearlog parameter destroys the contents of the CHALLENGE RAID SP’s
error log. To clear the event log, use
raid5 -d
device
clearlog
Note:
You must be root to use this parameter.
This command has no output.
clearstats
The clearstats parameter resets statistics logging on the CHALLENGE RAID
SP, resetting all log counters to 0. To reset statistics logging, use
raid5 -d
device
clearstats
Note:
You must be root to use this parameter.
This command has no output.
firmware
To update the firmware on the CHALLENGE RAID SP, type as root
raid5 -d
device
firmware /usr/raid5/flarecode.bin
Note:
The bus must be quiesced, with all applications disabled and only the
RAID agent running. You must use this command every time you replace a
failed unbound disk module (A0, B0, C0, or A3).
In this string, the new firmware image /usr/raid5/flarecode.bin contains
microcode that runs on the SP and also a microcode image destined for the
SP PROM, which runs the power-on diagnostics.