95
Operating limits
Ambient temperature
Relative humidity
Elevation
Heat dissipation
Shock
Vibration
10 degrees C to 38 degrees C
(50 degrees F to 100 degrees F)
20 to 80% noncondensing
2439 m (8000 ft)
3168 x 103 J/hr (3000 BTU/hr) max per
chassis assembly
3 g @ 11 ms
0.25 g peak @ 5 Hz to 500 Hz
Nonoperating limits
(shipping and
storing)
Ambient temperature
Gradient, maximum
Relative humidity
Elevation
-40 degrees C to 65 degrees C
(-40 degrees F to 149 degrees F)
24 C/hr (43.2 degrees F/hr)
10 to 90% noncondensing
7625 m (25,010 ft)
Physical
Cabinet dimensions
Maximum cabinet weight
See Table A-1 for weights
of FRUs.
Height: 180.34 cm (71.0 in)
Width: 58.42 cm (23.0 in)
Depth: 78.74 cm (31.0 in)
407.96 kg (899.4 lb): 4 chassis assemblies,
each with 20 disk modules, 2 SPs, 3 power
supplies, battery backup unit, without
packaging
Service clearance
Front access
Rear and side access
81.3 cm (32.0 in)
76.2 cm (30.0 in)
Buses
External host bus
Internal storage system
buses
Differential fast and wide SCSI-2
(synchronous)
Five single-ended SCSI buses
Table A-2 (continued)
CHALLENGE RAID Rack Specifications
Classification
Specification
Value