Page 8/44
1- 6 Equipment Overview
POS.
NAME
DESCRIPTION
A
Display
Backlighted display that shows all functions, measures and alarms about the generator and the mains.
Automatically the backlight turns off, and it turns on again when you press a button.
B
AUT
Button to select the automatic mode.
C
TEST
Button to select the test mode.
D
RESET
To activate reset/OFF mode. In this operative mode the remote start output is deactivated and the alarms
are deleted. If the cause of the alarm persists, the alarm will appear again.
E
KG
Key control to activate the remote start output (only in manual mode). With engine running, and in manual
test mode, this button permits to manage the generator contactor.
F
Menu
To enter the programmation menu. Inside the menus, it’s used as a button “back” or “esc”.
G
KG state led
Led that indicates if KG is closed (led on) or open (led off).
H
KR state led
Led that indicates if KR is closed (led on) or open (led off).
I
Help
From the main page of the menu, it permits to go directly to the active alarms page, if at least one alarm is
present.
J
KR
Key control to deactivate the remote start output (only in manual mode). If it’s pressed and released
quickly, it deactivates the output after the cooling time; if it’s pressed for 3 seconds, it deactivates the
output immediately. In manual test mode, this button permits to manage the mains contactor.
K
MAN
Button to select the manual mode.
L
Navigation drive
Navigation drive composed by 4 arrows to scroll through the pages (left and right arrows) and increase or
decrease the parameters inside the programmation menus. It contains also a special button “
i
”, to select
an element on the screen or edit a parameter and confirm the new value. See paragraph 1.8.1 for more
information about the navigation of the display pages, and paragraph 2-2 for more information about the
navigation through the menus.
M
Mains state led
It shows if the mains status:
led OFF if mains not detected
led blinking if mains detected outside limits
led ON if mains is within limits after delay
N
Generator state led
It shows the status of the generator:
led OFF if genset is not detected
led blinking if genset is running but not within limits
led ON if genset is within limits after delay
O
General alarm led
It blinks if a stopping alarm is present. It remains ON if an alarm enabled as global alarm 1 is present.
P
Battery state led
It turns on when the board is supplied.
B
A
D
E
K
C
G
F
J
I
H
L
M
N
O
P