2- 9 M7 - Connectivity
2- 9.1 M7.1 - Serial port setup
POS.
NAME
DESCRIPTION
RANGE OF
VALUES
DEFAULT
SETTINGS
A
Unit ID
It’s the address of the board for RS485 communication.
0-255
1
B
RS485 protocol
Protocol types available:
None:
Serial port disabled.
Modbus Master:
used for the connection with RI6010 expansion and Genset
Slave module for Dual standby mode.
Modbus slave:
used for remote monitoring via serial cable or Dual standby
connection with a master modbus device.
GSM modem:
used to connect GSM modem.
None
Modbus Master
Modbus Slave
Gsm modem
Modbus
Slave
C
RS485 baud-rate
Communication speed in bit per second: for modem connections, it is
recommended speed of 9600.
9600-115200 [bps]
115200
D
RS232 protocol
Protocol types available:
None:
Serial port disabled.
Modbus Master:
used for the connection with RI6010 expansion and Genset
Slave module for Dual standby mode.
Modbus slave:
used for remote monitoring via serial cable or Dual standby
connection with a master modbus device.
GSM modem:
used to connect GSM modem.
None
Modbus Master
Modbus Slave
Gsm modem
Modbus
Slave
E
RS232 baud-rate
Communication speed in bit per second for RS232 port.
9600-115200 [bps]
115200
F
Activate USB
Confirm to activate USB port to communicate with PC. The communication
channel disables as protection CAN port and current measures on J3, use it
without machine running for programmation only.
O
ff
-On
O
ff
G
232 parity
Set the parity for 232 serial port:
1 = Even
2 = Odd
3 = Mark
4 = Space
None - 4
None
H
485 parity
Set the parity for 485 serial port:
1 = Even
2 = Odd
3 = Mark
4 = Space
None - 4
None
I
Enable genset
It permits to enable (On) or disable (Off) the communication with a genset
engine protection controller, to see its measures about the engine and the main
alarms, and to send starting and stopping commands via RS485.
On-O
ff
O
ff