2- 8.4 M6.4 - TPS
This function similar to automatic test is used to program up to two working intervals which activate the generator at chosen clock time and stop it at
a chosen clock time. It's also possible to program if the working time is with or without load, with or without remote stop and which are the days
allowed to work.
POS.
NAME
DESCRIPTION
RANGE OF
VALUES
DEFAULT
SETTINGS
A 1-2
TPS1 start (h) - TPS1
start (m)
TPS1 start hour and minute.
0-23 / 0-59
8:30
B 1-2
TPS1 stop (h) - TPS1
stop (m)
TPS1 stop hour and minute.
0-23 / 0-59
12:30
C
TPS1 enable
If O
ff
, the working period 1 is disabled.
On-O
ff
O
ff
D
TPS2 start (h) - TPS2
start (m)
TPS2 start hour and minute.
0-23 / 0-59
14:30
E
TPS2 stop (h) - TPS2
stop (m)
TPS2 stop hour and minute.
0-23 / 0-59
18:30
F
TPS2 enable
If O
ff
, the working period 2 is disabled.
On-O
ff
O
ff
G
TPS with load
If On, the TPS mode will be with load on generator side, id Off the load will
remain on mains side and the changeover will happen only in case of mains
failure during TPS.
On-O
ff
O
ff
H
No remote stop
If On, the TPS mode will override remote stop activation to start the
generator.
On-O
ff
O
ff
POS.
NAME
DESCRIPTION
-
Sunday
If the tick is present, it enables the TPS on Sunday. If the tick is removed, on this day the TPS is not executed.
-
Monday
If the tick is present, it enables the TPS on Monday. If the tick is removed, on this day the TPS is not executed.
-
Tuesday
If the tick is present, it enables the TPS on Tuesday. If the tick is removed, on this day the TPS is not executed.
-
Wednesday
If the tick is present, it enables the TPS on Wednesday. If the tick is removed, on this day the TPS is not
executed.
-
Thursday
If the tick is present, it enables the TPS on Thursday. If the tick is removed, on this day the TPS is not executed.
-
Friday
If the tick is present, it enables the TPS on Friday. If the tick is removed, on this day the TPS is not executed.
-
Saturday
If the tick is present, it enables the TPS on Saturday. If the tick is removed, on this day the TPS is not executed.
2- 8.5 M6.5 - Hours
POS.
NAME
DESCRIPTION
RANGE OF
VALUES
DEFAULT
SETTINGS
A
Initial work
Here you can set a value of the work hours, then confirm the parameter D to
set the actual work hours to this value.
0-999999 [h]
0
B
KG hours
Here you can set a value of the work hours with KG closed, then confirm the
parameter D to set the actual work hours with KG closed to this value.
0-999999 [h]
0
C
KR hours
Here you can set a value of the hours with KR closed, then confirm the
parameter D to set the actual hours with KR closed to this value.
0-999999 [h]
0
D
Counter reset
Confirm this parameter to set the values at parameters A, B and C. It
becomes 1 for a small time after you confirmed it, to indicate that the
procedure of hours updating is working.
Wait…-Ok
Ok
E
Clear events log
If you confirm this option with "i" button, the events in the events log are
deleted.
-
Ok