![Sifam Tinsley ST 301 ATS Instruction Manual Download Page 40](http://html.mh-extra.com/html/sifam-tinsley/st-301-ats/st-301-ats_instruction-manual_1267037040.webp)
Page 40/44
Answer (identical message re transmitted after editing the register):
First measures registers which can be read with a single read holding register function of 44 registers starting from address 635 (634 if zero based
modbus):
Memory map
Var.Name - FIRST PACK
Description
Var.Visual
ID
R/W
Scale
Active program
Mode of operation GENSET:
0=Manual
1=Automatic
2=Reset
DT_NUMERIC
40635
R
1
Fuel level percentage
Fuel level percentage
DT_NUMERIC
40636
R
10
Not used
Not used
DT_NUMERIC
40637
R
1
Oil pressure
Oil pressure
DT_NUMERIC
40638
R
10
Engine temperature
Engine temperature
DT_NUMERIC
40639
R
1
Mains Line voltage L1-L2
Mains Line voltage L1-L2
DT_NUMERIC
40640
R
1
Mains Line voltage L2-L3
Mains Line voltage L2-L3
DT_NUMERIC
40641
R
1
Mains Line voltage L3-L1
Mains Line voltage L3-L1
DT_NUMERIC
40642
R
1
Mains phase voltage L1
Mains phase voltage L1-N
DT_NUMERIC
40643
R
1
Mains phase voltage L2
Mains phase voltage L2-N
DT_NUMERIC
40644
R
1
Mains phase voltage L3
Mains phase voltage L3-N
DT_NUMERIC
40645
R
1
Mains frequency
Mains frequency
DT_NUMERIC
40646
R
10
Mains kWh
Mains kWh
DT_NUMERIC
40647
R
1
Generator Line voltage L1-L2
Generator Line voltage L1-L2
DT_NUMERIC
40648
R
1
Generator Line voltage L2-L3
Generator Line voltage L2-L3
DT_NUMERIC
40649
R
1
Generator Line voltage L3-L1
Generator Line voltage L3-L1
DT_NUMERIC
40650
R
1
Generator phase voltage L1
Generator phase voltage L1-N
DT_NUMERIC
40651
R
1
Generator phase voltage L2
Generator phase voltage L2-N
DT_NUMERIC
40652
R
1
Generator phase voltage L3
Generator phase voltage L3-N
DT_NUMERIC
40653
R
1
Generator frequency
Generator frequency
DT_NUMERIC
40654
R
10
Generator kWh
Generator kWh
DT_NUMERIC
40655
R
1
Not used
Not used
DT_NUMERIC
40656
R
1
Battery voltage
Battery voltage
DT_NUMERIC
40657
R
10
Not used
Not used
DT_NUMERIC
40658
R
1
Work hours
Work hours
DT_NUMERIC
40659
R
1
Not used
Not used
DT_NUMERIC
40660
R
1
Not used
Not used
DT_NUMERIC
40661
R
1
Test mode on
Test mode on
DT_NUMERIC
40662
R
1
IO status:
Bit0= Input 4.4
Bit1= Input 4.5
Bit2= Input 4.6
Bit3= Input 4.7
Bit4= Input 4.8
Bit5= Input 6.2
Bit6= Input 6.3
Bit7= Input 6.4
Bit8= Output 5.8
Bit9= Output 5.9
Bit10= Output 5.10
Bit11= Output 5.11
Bit12= Output KR
Bit13= Output KG
Bit14= Output 5.5
BIt15= Output 5.4
Status of inputs and outputs
0=Not active
(closed if NC - open if NO)
1=Active
(closed if NO – open if NC)
DT_NUMERIC
40663
R
Bin
Load current L1
Load current L1
DT_NUMERIC
40664
R
1
Load current L2
Load current L2
DT_NUMERIC
40665
R
1
Load current L3
Load current L3
DT_NUMERIC
40666
R
1
Total load current
Total load current
DT_NUMERIC
40667
R
1
Total active power
Total active power
DT_NUMERIC
40668
R
1
Total reactive power
Total reactive power
DT_NUMERIC
40669
R
1
Total apparent power
Total apparent power
DT_NUMERIC
40670
R
1
Not used
Not used
DT_NUMERIC
40671
R
10
Not used
Not used
DT_NUMERIC
40672
R
1
Not used
Not used
DT_NUMERIC
40673
R
10
Not used
Not used
DT_NUMERIC
40674
R
10
Not used
Not used
DT_NUMERIC
40675
R
10
Total power factor
Total power factor
DT_NUMERIC
40676
R
100
Not used
Not used
DT_NUMERIC
40677
R
1
Not used
Not used
DT_NUMERIC
40678
R
1
Var.Name - SECOND PACK
Description
Var.Visual
ID
R/W
Scale
Active power L1
Active power L1
DT_NUMERIC
40727
R
1
Active power L2
Active power L2
DT_NUMERIC
40728
R
1
Active power L3
Active power L3
DT_NUMERIC
40729
R
1
Apparent power L1
Apparent power L1
DT_NUMERIC
40730
R
1
Apparent power L2
Apparent power L2
DT_NUMERIC
40731
R
1
Slave
address
Function
Address of the desired
register
Value to set in the
register
CRC checksum