2- 10.2 M8.2 - Output setup
The Output setup permits to select the type of use of the programmable outputs.
The outputs O5.8, O5.9, O5.10, O5.11, O5.5 and O5.4 can be programmed as:
None: no function associated to the output
Start: the output is used to command the start of the genset to the engine protection controller
Siren: the output is used to command a siren that sounds when an alarm with siren enabled appears
Global alarm 1: the output is used to command an indication when an alarm set as general alarm 1 appears. The output remains active until you
reset or the alarm disappears
Engine running: the output is activated when the generator is running
Test active: the output is used to signal that the test is active
Dummy load: the output is used for the dummy load function. To have more information about this function, see menu 2-8.3
O
ff
mode: indicates that the controller is in o
ff
/reset mode
Auto mode: indicates that the controller is in automatic mode
Man mode: indicates that the controller is in manual mode
Global alarm 2: the output is used to command an indication when an alarm set as general alarm 2 appears. The output remains active until you
reset or the alarm disappears
Global alarm 3: the output is used to command an indication when an alarm set as general alarm 3 appears. The output remains active until you
reset or the alarm disappears
KG active: indicates that the generator contactor is closed
KR active: indicates that the mains contactor is closed
Alarm A: the output is active when the alarm assigned to A position by M8.2 - g parameter is active
Alarm B: the output is active when the alarm assigned to B position by M8.2 - h parameter is active
Alarm C: the output is active when the alarm assigned to C position by M8.2 - i parameter is active
Start failure: indicates that the generator is not detected running after the starting procedure
Electrical trip: the output is activated if the Electrical trip alarm is active
GE.ready: the output is activated when the generator is ready to take the load
POS.
NAME
RANGE OF VALUES
DEFAULT SETTINGS
A
O5.8
None - Start - Siren - Global alarm 1 - Engine running - Test active - Dummy load - O
ff
mode
- Auto mode - Man mode - Global alarm 2 - Global alarm 3 - KG active - KR active - Alarm A
- Alarm B - Alarm C - Start failure - Electrical trip – GE ready
Global alarm 1
B
O5.9
Same as parameter A
Auto mode
C
O5.10
Same as parameter A
Man mode
D
O5.11
Same as parameter A
Siren
E
O5.5
Same as parameter A
Start failure
F
O5.4
Same as parameter A
Start
G
Alarm A
[O
ff
- 64] - see single alarm ID list below
O
ff
H
Alarm B
[O
ff
- 64] - see single alarm ID list below
O
ff
I
Alarm C
[O
ff
- 64] - see single alarm ID list below
O
ff