2- 7 M5 - Alarms list
The alarms setup is composed by 4 different alarm groups:
a)
Mains alarms
b)
Generator alarms
c)
Engine alarms
d)
General alarms
Select the category with the down and up arrows, then press “i” to confirm and enter.
You will see a general screen for the setup of the alarms, composed by 4 pages. In the first page, select and confirm the parameter “a” to choose
the code of the alarm. In the upper part of the screen you will see the name of the correspondent alarm. Then modify the parameters from “d” to “l”
as you prefer. Return then to the first page and confirm the parameter “c” to save the modifications.
For every alarm, you can program all the following parameters:
POS.
NAME
DESCRIPTION
RANGE
A
Alarm code
Select this parameter to choose the alarm that you want to set. All the parameters in the
next pages refer to the alarm selected in this parameter. In the upper part of the screen you
will see also the name correspondent to the code that you are selecting.
-
B
Category of the alarm
Name of the category selected from the first screen of the alarm setup. It’s not possible to
modify it directly in this page.
-
C
Save alarm
Parameter that has to be confirmed with the “i” button to save all the parameters from D to
L in the configuration of the alarm selected at parameter A.
-
D
Activation
It permits to choose when the alarm condition must be verified and make the alarm appear:
Always (always enabled), Run (active only with engine running) or Disabled (disabled).
Always - Run-
Disabled
E
Delay
Before the activation of the alarm, the cause must remain present for this time.
0-255 [s]
F
Retentive
Choose if the alarm must be retentive (ON: the alarm indication remains on display until
you press the reset button, even if the cause has disappeared) or not (OFF: the alarm
indications disappears when the cause disappears).
O
ff
-On
G
Action
Select the action in consequence of the activation of the alarm: Warning (only indication),
Stop (the alarm stops the engine immediately) or Cooling (the alarms stops the engine with
cooling).
Warning - Stop
- Cooling
H
Siren
Set if the activation of the alarms must also activate the output programmed for Siren. It
can be set to ON (the output set for “siren” is activated when the alarm is present) or OFF.
O
ff
-On
I
Remote
Set if the activation of the alarm must also send an SMS message if Remote APP option is
enabled and one or more of programmed GMS numbers are correctly saved (see menu
M7). It can be set to ON (if a modem is connected, the board sends a SMS when the alarm
appears) or OFF. Enable also the single alarm flag inside modbus map.
O
ff
-On
J
Global 1
Set if the activation of the alarms must also activate the output programmed for Global
alarm 1. It can be set to ON (the output is activated when the alarm is present) or OFF.
O
ff
-On
K
Global 2
Set if the activation of the alarms must also activate the output programmed for Global
alarm 2. It can be set to ON (the output is activated when the alarm is present) or OFF.
O
ff
-On
L
Global 3
Set if the activation of the alarms must also activate the output programmed for Global
alarm 3. It can be set to ON (the output is activated when the alarm is present) or OFF.
O
ff
-On