![Sifam Tinsley ST 301 ATS Instruction Manual Download Page 32](http://html.mh-extra.com/html/sifam-tinsley/st-301-ats/st-301-ats_instruction-manual_1267037032.webp)
Page 32/44
2- 9.2.2 - SMS commands list
This is the list of commands which could be sent to mobile device:
COMMAND NAME
TEXT SENT
(case sensitive)
DESCRIPTION
MANUAL MODE
MAN
Activate manual mode on remote device
AUTO MODE
AUT
Activate auto mode on remote device
OFF MODE
OFF
Activate O
ff
mode on remote device
RESET ALARMS
RESET
Alarms reset on remote device
MAINS CONTACTOR
MAINS
Changeover switch on mains side in manual mode
GENSET CONTACTOR
GEN
Changeover switch on generator side in manual
mode
START ENGINE
START
Start generator command in manual mode (if man
mode is not selected, the controller will activate
manual mode before start)
STOP ENGINE
STOP
Stop generator command in manual mode (if man
mode is not selected, the controller will activate
manual mode before start)
TEST MODE
TEST
Activate test mode
NAME
NAME:[name_parameter]
Name_paramete is max 16 characters string
Set remote device name
CUSTOM PARAMETER
SET:[ID_parameter] [Value_parameter]
Both values are numeric between 0-9999; for example if I
want to set parameter 300 to 10, the text sent will be:
SET:300 10
Set an enabled parameter of remote device.
Warning: consult the correct memory map to
verify the address of the parameter you want
to modify. A wrong setting could compromise
the functioning of the machine.
SET GSM NUMBER
SET[Position_number]:[Cellphone_number]
Position_number value is numeric between 1-6,
cellphone_number is a telephone number which allows the
remote device to know where SMS need to be sent.
For instance to set number 339 333 9000 in position #3 of
remote device, the sent text will be:
SET3:3393339000
Set the telephone number which will be used by
remote device to send SMS. Usually this number
is the one of the receiver device where the app is
installed.
SYSTEM INFO
INFO
Command to request info to the remote device.
2- 9.3 M7.3 - Datalogger
POS.
NAME
DESCRIPTION
RANGE OF
VALUES
DEFAULT
SETTINGS
A
Enable datalog
Enable automatic datalog.
O
ff
-On
O
ff
B
Sample time (s)
Set the sampling time for datalog, change this value with datalog disabled. Then
enable datalog with the new value.
The datalog memory size is 1588 samples, when the memory is full, no more
samples are taken and an erase memory must be performed before start sampling
again, below a table of sampling intervals with time by hours and days before
fulfilling the memory size:
Sample time (s)
Hours to full
memory
Days to full
memory
Samples per day
10
4,41
0,18
8640,00
60
26,47
1,10
1440,00
300
132,33
5,51
288,00
600
264,67
11,03
144,00
1800
794,00
33,08
48,00
3600
1588,00
66,17
24,00
7200
3176,00
132,33
12,00
12400
5469,78
227,91
6,97
14400
6352,00
264,67
6,00
[5-65535]
12400