SXL-EX
Operation, Installation, and Maintenance Manual
3. Press the
Drill
key to change the state of
the selected output.
4. Press the
ACK
key when done.
Test Level 4 - Last Event Record
1. Press the
Reset
key 4 times to select
Test Level 4.
2. Press the
Silence
key to select the event
to be reviewed per the following table:
Example:
4-1 reviews the last zone in
alarm.
Level
Feature
4-1
Review Last Alarm
4-2
Review Last Zone Trouble
4-3
Review Last Verification
4-4
Review Last Supervisory
3. The Zone Alarm LED for the last zone in
alarm will be on. Similarly, the Zone
Trouble LED will be on for the last zones
in supervisory and trouble conditions.
4. Press the
ACK
key when done.
Test Level 5 - Lamp Test
1. Press the
Reset
key 5 times to select
Test Level 5.
2. Press the
Silence
key to select the lamps
to be tested as indicated in the following
table:
Example:
5-1 tests Local Display.
Level
Feature
5-1
Test the Local Display
5-2
Test Remote Annunciators
3. Press and hold the
Drill
key to turn the
lamps on.
4. Press the
ACK
key when done.
Test Level 6 - Clear the Last Event
Record
1. Press the
Reset
key 6 times to select
Test Level 6.
2. Press the
Silence
key to select this
function. There is no other function to be
selected.
3. Press the
Drill
key to clear the event
record.
4. Press the
ACK
key when done.