17
SXL-EX Operation, Installation, and Maintenance Manual
3. The red zone LED for the selected Output
will be on if the Output is enabled and off
if bypassed.
4. Press the
Drill
key to change the state of
the Output.
5. Press the
Silence
key to select another
Output to be bypassed and return to Step
3.
6. Press the
ACK
key when done.
Program Level 3 - Set Zone Types
1. Press the
Reset
key 3 times to select
Program Level 3.
2. Press the
Silence
key to select the Zone
to be programmed.
Example:
3-1 programs the Zone Type
for Zone 1.
3. The selected Zone Type is shown by the
red zone LED indicated in the following
table:
Zone 1 LED
=
Initiating Zone Type
Zone 2 LED
=
Verified Alarm Zone Type
Zone 3 LED
=
Supervisory Zone Type
Zone 4 LED
=
Generic Zone Type
4. Press the
Reset
key to advance the
pointer (yellow zone LED) to the desired
Zone Type.
5. Press the
Drill
key to activate the desired
Zone Type.
6. Press the
Silence
key to select another
Zone to be programmed and return to
Step 3.
7. Press the
ACK
key when done.
Program Level 4 - Set NAC Types
1. Press the
Reset
key 4 times to select
Program Level 4.
2. Press the
Silence
key to select the NAC
to be programmed.
Example:
4-1 programs the NAC type for
the first Bell Circuit.
3. The selected NAC type is shown by the
red zone LED indicated in the following
table:
Zone 1 LED
=
Steady NAC
Zone 2 LED
=
Temporal Code
Zone 3 LED
=
March Time Code
Zone 4 LED
=
Simple Zone Code
Zone 5 LED
=
Non-Silenceable Output
4. Press the
Reset
key to advance the
pointer (yellow zone LED) to the desired
NAC type.
5. Press the
Drill
key to activate the desired
NAC type.
6. Press the
Silence
key to select the other
NAC to be programmed and return to
Step 3.
7. Press the
ACK
key when done.
Program Level 5 - Output Control
Matrix
1. Press the
Reset
key 5 times to select
Program Level 5.
2. Press the
Silence
key to select the Zone
to be programmed.
Ex: 5-1 allows mapping Zone 1 to
Outputs.
3. The selected Zone Map is shown by the
red zone LEDs indicated in the following
table:
Zone 1 LED = Zone Mapped to Output 1
Zone 2 LED = Zone Mapped to Output 2
Zone 3 LED = Zone Mapped to Output 3
Zone 4 LED = Zone Mapped to Output 4
Zone 5 LED = Zone Mapped to Output 5
Zone 6 LED = Zone Mapped to Output 6
Zone 7 LED = Zone Mapped to Output 7
Zone 8 LED = Zone Mapped to Output 8
4. Press the
Reset
key to advance the
pointer (yellow zone LED) to the desired
Output.